ABBREVIATIONS ELECTRICAL SYMBOL LEGEND TELEPHONE SYSTEM NOTES LEED SYSTEM COMMISSIONING GENERAL ELECTRICAL NOTES A�
<br /> AFF ABOVE FINISHED FLOOR O JUNCTON BOX RECEPTACLE: DUPLEX IF ADDITIONAL TELEPHONE LINES ARE REQUIRED BEYOND THE STANDARD CONTRACTOR RESPONSIBILITIES FOR BUILDING COMMISSIONING 1. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL
<br /> AHJ AUTHORITIES HAVING JURISDICTION SINGLE LINE(SUCH AS FOR A FIRE ALARM)THE GENERAL CONTRACTOR WORK AND SPECIFICATIONS WITH OTHER TRADES. THE
<br /> APPROX APPROXIMATE SHALL CONTACT STARBUCKS PRIOR TO BEGINNING CONSTRUCTION TO CONTRACTOR SHALL PROVIDE SUPPORT AND WORK AS SPECIFIED, NEEDED ARCHITECTURAL DRAWINGS AND SPECIFICATIONS SHALL TAKE
<br /> ORDER THE ADDITIONAL TELEPHONE LINE(S). REPORT ANY TELEPHONE AND REQUIRED TO CONDUCT AND FACILITATE STARBUCKS STAFF BUILDING PRECEDENCE OVER ALL OTHER DRAWINGS. DO NOT SCALE
<br /> BLDG BUILDING $ SWITCH (# RECEPTACLE: DUPLEX- INSTALLATION ISSUES IMMEDIATELY TO STARBUCKS. COMMISSIONING EFFORTS.THIS WORK WILL BE COMPRISED OF THREE DISTANCES OFF THE ELECTRICAL DRAWINGS; USE ACTUAL BUILDING
<br /> INDIVIDUAL BRANCH CIRCUIT DISTINCT EFFORTS: DIMENSIONS. OVERALL CASEWORK COMPONENT DIMENSIONING ON
<br /> CKT CIRCUIT CONFIRM PRIOR TO BEGINNING CONSTRUCTION THAT THERE ARE 1) SUPPORT STARBUCKS COMMISSIONING AGENT(CXA)DURING ELECTRICAL DETAILS ARE SHOWN FOR REFERENCE AND
<br /> CLG CEILING THREE-WAY SWITCH RECEPTACLE: QUAD EXISTING,WORKING TELCO FACILITIES TO THE BUILDING OR THAT INSTALLATION VERIFICATION AND CORRECT DISCLOSED DEFICIENCIES; COORDINATION ONLY. SEE SPECIFICATION SHEETS FOR
<br /> CM STARBUCKS CONSTRUCTION MANAGER # LANDLORD HAS FURNISHED AND INSTALLED ONE(1)2"(51MM)MIN. 2) PERFORM TESTING,ADJUSTING, BALANCING AND SYSTEM STARTUP AND ELECTRICAL SPECIFICATIONS
<br /> CONST CONSTRUCTION (ENTRANCE)CONDUIT INCLUDING PULL STRING FROM TELCO STREET FEED SUPPORT FUNCTIONAL PERFORMANCE TESTING BY STARBUCKS CXA;
<br /> CW COLD WATER LINE TO THE BUILDING AS IDENTIFIED BY THE PHONE COMPANY. NOTIFY 3) CORRECT DEFICIENCIES DISCLOSED BY FUNCTIONAL PERFORMANCE 2. ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER ©2017 STARBUCKS COFFEE COMPANY
<br /> CXA COMMISSIONING AGENT MOTION (OCCUPANCY) # RECEPTACLE: QUAD- STARBUCKS CONSTRUCTION MANAGER IMMEDIATELY IF FACILITIES OR TESTING AND SUBMIT REPORTS. CONTRACTOR SHALL PERFORM AND OPERATION. BALANCE ALL BRANCH CIRCUIT LOADS BETWEEN THE
<br /> SENSOR SWITCH INDIVIDUAL BRANCH CIRCUIT COUDUIT AND PULL STRING ARE NOT INSTALLED. PROVIDE THE FOLLOWING: PHASES OF THE SYSTEM WITHIN 10%OF THE HIGHEST PHASE LOAD
<br /> DEG DEGREES IN EACH PANEL BOARD. STARBUCKS COFFEE
<br /> DL LIGHTS WITHIN DAYLIGHT ZONE O SWITCHBACK RECEPTACLE: HIGH VOLTAGE GENERAL CONTRACTOR IS TO ENSURE THAT THERE IS A 2"(51 MM)MIN. A. SYSTEMS SUBJECT TO COMMISSIONING MAY INCLUDE, BUT ARE NOT
<br /> DM STARBUCKS DESIGN MANAGER CONDUIT WITH PULL STRING FROM THE DATA RACK TO THE DEMARC LIMITED TO DOMESTIC HOT WATER GENERATION, HVAC SYSTEMS, 3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR DE- COMPANY
<br /> ON DOWN (TELCO TO CUSTOMER HAND OFF EQUIPMENT)WHEN THE DEMARC IS ROOFTOP UNITS, EXHAUST FANS,HVAC CONTROLS,LIGHTING ENERGIZING CIRCUITS IN DEMOLITION AREAS TO INSURE A SAFE
<br /> DTL DETAIL MORE THAN 10'FROM THE DATA RACK. DISTANCES LESS THAN 10'WILL CONTROLS,AIR CURTAINS,BUILT-IN REFRIGERATION EQUIPMENT, CONDITION. ELECTRICAL DEVICES AND ASSOCIATED WIRING 2401 UTAH AVENUE SOUTH
<br /> DWG(S) DRAWING(S) - TELEPHONE ® RECEPTACLE: FLOOR DUPLEX NOT REQUIRE CONDUIT. AND RENEWABLE ENERGY SYSTEMS. LOCATED WITHIN THE DEMOLITION AREA THAT WILL NO LONGER BE SEATTLE, WASHINGTON 98134
<br /> USED SHALL BE REMOVED AND PROPERLY DISPOSED OF AT 206 318-1575
<br /> EA EACH PROVIDE A 3-POSITION GROUND LUG, GROUNDED WITH#6 AWG GROUND B. CONTRACTOR SHALL INCLUDE COMMISSIONING ACTIVITIES IN CONTRACTORS EXPENSE UNLESS OTHERWISE NOTED.
<br /> EC ELECTRICAL CONTRACTOR OT THERMOSTAT GROUNDING ELECTRODE WIRE, IF REQUIRED BY TELEPHONE COMPANY. PROJECT SCHEDULE AND SHOW INTERVALS FOR PERFORMANCE THESE DRAWINGS AND SPECIFICATIONS ARE
<br /> ECP EQUIPMENT CONTROL PAC — CONNECTION OF WORK FOR WHICH CONTRACTOR IS RESPONSIBLE AND 4. THE ELECTRICAL CONTRACTOR SHALL SCHEDULE ALL ELECTRICAL CONFIDENTIAL AND SHALL REMAIN THE SOLE
<br /> EG EXHAUST GRILLE ALL TELEPHONE/NETWORK CABLING IS THE SCOPE OF WORK OF THE INTERVALS FOR WORK PERFORMED BY STARBUCKS CXA. SYSTEM OUTAGES WITH THE GENERAL CONTRACTOR AND
<br /> ELEC ELECTRICAL TELEPHONE/NETWORK CABLING VENDOR. CONTRACTOR SHALL SHOW RESOURCES FOR PERFORMING ALL LANDLORD AT LEAST 24 HOURS IN ADVANCE. UNLESS APPROVED PROPERTY OF STARBUCKS CORPORATION,
<br /> EM EMERGENCYSO THERMOSTAT SENSOR NL NIGHTLIGHTING 24HR/DAY WORK RELATED TO COMMISSIONING ACTIVITIES ON A LINE ITEM IN OTHERWISE ALL OUTAGES SHALL OCCUR BETWEEN 11:OOPM AND WHICH IS THE OWNER OF THE COPYRIGHT IN
<br /> EMS ENERGY MANAGEMENT SYSTEM THE SCHEDULE OF VALUES. 5:OOAM. THIS WORK. THEY SHALL NOT BE
<br /> EXIST EXISTING REPRODUCED(IN WHOLE OR IN PART),SHARED
<br /> EXT EXTERIOR DIMMER SWITCHPE PHOTOELECTRIC CELL C. CONTRACTOR SHALL INSTALL EQUIPMENT IN ACCORDANCE WITH 5. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL WITH THIRD PARTIES OR USED IN ANY MANNER
<br /> POS \ DATA LINE NOTES THE MANUFACTURER'S REQUIREMENTS AND ALL CONTRACT NECESSARY CONDUIT AND J-BOXES TO SUPPORT A COMPLETE ON OTHER PROJECTS OR EXTENSIONS TO THIS
<br /> F&I FURNISH&INSTALL DOCUMENTS. ENSURE THAT ALL EQUIPMENT IS INSTALLED TOTALLY SECURITY, PHONE, POS AND DATA SYSTEMS. SEE MANAGER PROJECT WITHOUT THE PRIOR WRITTEN
<br /> FLR FLOOR COMPLETE,AND ACCESSIBLE TO STARBUCKS CXA FOR WORKSTATION AND BAR POINT OF SALE(POS) CONSENT OF STARBUCKS CORPORATION.
<br /> FT FOOT/FEET ® RECEPTACLE: DATA (p} SPEAKER STARBUCKS CONTRACTS DIRECTLY WITH THE DATA CABLING VENDOR TO INSTALLATION VERIFICATION AND FUNCTIONAL PERFORMANCE POWER/TELECOM/SECURITY DIAGRAM. COORDINATE ALL DEVICE THESE DRAWINGS AND SPECIFICATIONS ARE
<br /> SUPPLY AND INSTALL CATEGORY 5e(CAT5e)LAN CABLE AND TESTING PRIOR TO THE SCHEDULED START OF INSTALLATION LOCATIONS AND MOUNTING HEIGHTS WITH SECURITY VENDOR PRIOR INTENDED TO EXPRESS DESIGN INTENT FOR A
<br /> GC GENERAL CONTRACTOR CONNECTORS FOR THE POINT OF SALE (POS)SYSTEMS. CONTRACTOR TO VERIFICATION. TO ROUGH-IN. PROVIDE END-TO-END PULL STRINGS IN ALL PROTOTYPICAL STARBUCKS STORE (WHICH IS
<br /> GFCI GROUND FAULT CIRCUIT INTERRUPTER RACEWAY CONCEALED IN CEILING OR WALL. HASH MARKS SCHEDULE INSTALLATION OF DATA CABLING WITH DATA CABLING VENDOR. CONDUITS. LABEL EACH END OF THE PULL STRING WITH CONDUIT SUBJECT TO CHANGE AT ANYTIME)AND DO
<br /> GND GROUND INDICATE NUMBER DATA CABLING VENDOR REQUIRES A LEAD TIME FOR INSTALLATION. DATA D. INSTALLATION VERIFICATION SHALL BE PERFORMED BY STARBUCKS SYSTEM ("SECURITY")AND DESTINATION ("CAFE", "FRONT BAR",ETC.). NOT REFLECT ACTUAL SITE CONDITIONS.
<br /> OF WIRES. #12 AWG WIRE UNLESS OTHERWISE NOTED. TWO CABLING VENDOR WILL COORDINATE REGIONAL INSTALLERS. CXA. CONTRACTOR SHALL SUPPORT STARBUCKS CXA PROVIDE INSULATED BUSHINGS ON ALL STUBBED-UP AND EXPOSED NEITHER PARTY SHALL HAVE ANY OBLIGATION
<br /> HR HOUR WIRES PLUS INSTALLATION VERIFICATION EFFORTS AS NECESSARY.PROVIDE CONDUIT ENDS. NOR LIABILITY TO THE OTHER(EXCEPT STATED
<br /> HVAC HEATING,VENTILATION,AIR CONDITIONING GROUND IF NO HASH MARKS SHOWN. LONG HASH MARK AT THE START OF CONSTRUCTION, STARBUCKS CONSTRUCTION MANAGER ALL ACCESS AND EQUIPMENT NECESSARY FOR STARBUCKS STAFF ABOVE)UNTIL A WRITTEN AGREEMENT IS
<br /> HW HOT WATER DENOTES NEUTRAL. SCHEDULES DELIVERY OF CASH REGISTER/MANAGER'S WORKSTATION TO VERIFY THAT THE EQUIPMENT IS INSTALLED CORRECTLY. 6. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE GENERAL FULLY EXECUTED BY BOTH PARTIES.
<br /> GROUND WIRE NOT SHOWN. EQUIPMENT AND INSTALLATION BY A POS INSTALL TECHNICIAN FOR ONE CONTRACTOR TO PATCH AND REPAIR ALL EXISTING WALLS, FLOORS,
<br /> LCP LIGHTING CONTROL PANEL (1)MONTH PRIOR TO STORE OPEN. CONTRACTOR TO VERIFY DELIVERY E. CONTRACTOR SHALL BE READILY AVAILABLE DURING INSTALLATION CEILINGS OR OTHER SURFACES IDENTIFIED TO REMAIN THAT MAY
<br /> LL LANDLORD SCHEDULE TWO(2)WEEKS PRIOR TO DELIVERY AND INSTALLATION DATE. VERIFICATION TO CORRECT ANY DEFICIENCIES OR DEFECTS BECOME DAMAGED DURING THE COURSE OF WORK. STARBUCKS TEMPLATE VERSION 12017.05.18
<br /> LS LIGHT SENSOR PHOTOCELL EQUIPMENT IS SHIPPED DIRECTLY TO THE STORE. CONTRACTOR TO DISCLOSED BY THE INSTALLATION VERIFICATION PROCESS.
<br /> LV LOW VOLTAGE SECURITY SYSTEM NOTES ACCEPT POS EQUIPMENT DELIVERY. DO NOT REFUSE DELIVERY. CORRECTIONS SHALL BE MADE IN A TIMELY MANNER WITHOUT 7. EXPOSED/SURFACE MOUNTED CONDUITS SHALL ONLY BE ALLOWED
<br /> DISRUPTION OF THE CONSTRUCTION SCHEDULE. WHERE NECESSARY IN EXPOSED CEILING AREAS. IF CONDUITS
<br /> MAX MAXIMUM DATA CABLING TECHNICIAN TO PROVIDE ALL CAT5e LAN CABLING AND NEED TO BE SURFACE MOUNTED TO WALLS, COORDINATE WITH
<br /> MC MECHANICAL CONTRACTOR STARBUCKS CONTRACTS DIRECTLY WITH SECURITY VENDOR TO SUPPLY CONNECTORS FROM ALL DESIGNED AND FUTURE CASH REGISTER F. ALL HVAC, EXHAUST FAN,AND AIR CURTAIN EQUIPMENT SHALL BE STARBUCKS CONSTRUCTION MANAGER FOR APPROVAL.
<br /> MDP MAIN DISTRIBUTION PANEL AND INSTALL THE SECURITY SYSTEM.CONTRACTOR TO SCHEDULE LOCATIONS, MANAGER'S WORKSTATION,ALL OTHER NETWORKED TESTED,ADJUSTED AND BALANCED BY THE CONTRACTOR'S
<br /> MECH MECHANICAL INSTALLATION OF SECURITY SYSTEM FOR FOUR(4)TIMES; EQUIPMENT(CUP LABELERS, CLOVER, BUMP BAR, ETC...)AND WIRELESS TESTING,ADJUSTING AND BALANCE AGENT(SEE TESTING, 8. VERIFY LOCATION OF ALL OUTLETS AND SWITCHES WITH
<br /> MEP MECHANICAL, ELECTRICAL,AND PLUMBING 1. MEET TO PLAN SECURITY CABLE PULL WITH SECURITY CABLE ACCESS POINT TO THE DATA RACK AREA. CONTRACTOR IS TO HAVE ADJUSTING AND BALANCING)AFTER THE SYSTEM IS VERIFIED TO BE ARCHITECTURAL DRAWINGS, INTERIOR DETAILS, FINISH SCHEDULES,
<br /> MFG MANUFACTURER INSTALLER PRIOR TO DRYWALL INSTALLATION. CONDUIT WITH PULL STRING IN PLACE FOR ALL CABLE RUNS PRIOR TO COMPLETE AND CORRECT BY STARBUCKS CXA, IN ACCORDANCE GENERAL CONTRACTOR, EQUIPMENT VENDORS, STARBUCKS AND
<br /> MIN MINIMUM 2. SECURITY CABLE INSTALLER PULLS SECURITY CABLES,MOUNTS CABLE INSTALL DATE. WITH THE REQUIREMENTS OF THESE DOCUMENTS.ALL HVAC EXISTING SITE CONDITIONS. VERIFY FINAL DOOR HINGE LOCATION
<br /> PANEL, KEYPAD AND SENSORS. CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL PRIOR TO SWITCH INSTALLATION AND ADJUST SWITCH LOCATION IF
<br /> NL NIGHTLIGHT 3. SECURITY EQUIPMENT INSTALL OF CAMERA, NVR AND MONITOR. STARBUCKS NEW STORE GROUP IS RESPONSIBLE FOR COORDINATING DEVICES,COMPONENTS, EQUIPMENT AND SYSTEMS ARE NEEDED. DO NOT MOUNT RECEPTACLES/SWITCHES IN LOCATIONS
<br /> NTS NOTTO SCALE 4. SECURITY MONITORING COMPANY TO BRING SYSTEM ONLINE AND STARBUCKS POS SYSTEMS DELIVERY AND INSTALLATION WITH THE POS CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE WITH THAT WOULD CONFLICT WITH MIRRORS,SEAMS OF WALLS,
<br /> TRAIN PARTNERS AFTER POS INSTALL. VENDOR. THIS GROUP MAY BE CONTACTED AT: THESE PLANS AND SPECIFICATIONS. SEQUENCES OF OPERATION WAINSCOTS,TILE TRANSITIONS, ETC. ACIES
<br /> OCP OVERCURRENT PROTECTION NEWSTORES@STARBUCKS.COM. SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN paoressp4.
<br /> SECURITY VENDOR REQUIRES A MINIMUM TWO(2)WEEKS LEAD TIME FOR ACCORDANCE WITH THE CONTRACT REQUIREMENTS.
<br /> REF REFERENCE EACH INSTALLATION. SECURITY VENDOR WILL COORDINATE REGIONAL DELIVERABLES: PRELIMINARY,WRITTEN TESTING AND AIR BALANCE ENGINEERING o g
<br /> REQ(D) REQUIRE(D) INSTALLERS. ALL ADDITIONAL EXPENSES INCURRED DUE TO THE REPORT CONFORMING TO THE REQUIREMENTS SPECIFIED HEREIN, 337101con Street v
<br /> REV REVISION CONTRACTOR'S FAILURE TO SCHEDTRACT LE ACCORDINGLY WILL BE THE DOCUMENTING COMMUNICATION SYSTEM NOTES STARBUCKS CXAFIMMEDIA ELY UPON COMPLETION OF THE WORK. GENERAL NOTES E INFORMATION SPECIFIED, ETC.TO THE Sarna40)52 -Qm,GA 95054
<br /> RESPONSIBILITY AILUROF CONTRACTOR. ph:(4981522-5255 'mss s
<br /> SF SQUARE FEET A:(408)522-52M 8FC1R��� c
<br /> info@aues.pet �F P
<br /> 6
<br /> SPT SHEET CONFIRM PRIOR TO BEGINNING CONSTRUCTION THAT THE LANDLORD HAS G. CONTRACTOR SHALL INFORM STARBUCKS CXA WHEN EQUIPMENT IS SCOPE copyngnt©zola
<br /> SPECS SPECIFICATION(S) READY FOR FUNCTIONAL PERFORMANCE TESTING.ALL EQUIPMENT THE INTENT OF THE SPECIFICATION AND THE DRAWINGS IS TO PROVIDE A
<br /> SST STAINLESS STEEL CARBON MONOXIDE FURNISHED ANDING PULL ONE (FOR
<br /> ADDITIONAL OF TWO
<br /> FROM
<br /> TO STARTING TESTING.
<br /> FOR FUNCTIONAL
<br /> RACTOPERFORMANCE
<br /> OPERATE
<br /> PRIOR
<br /> CONDUIT INCLUDING PULL STRING(FOR A TOTAL OF TWO(2))FROM THE COMPLETE AND FULLY OPERATIONAL ELECTRICAL SYSTEM.THE ELECTRICAL
<br /> (CO) DETECTOR NOTES STREET FEED TO THE BUILDING AS IDENTIFIED BY THE INTERNET SERVICE TO STARTING ESTING.CONTRACTOR SHALL OPERATE EQUIPMENT CONTRACTOR SHALL FURNISH AND INSTALL ALL LABOR, MATERIAL,AND
<br /> TEL TELEPHONE PROVIDER. FOR STARBUCKS CXA AND VERIFY BY DEMONSTRATION THE EQUIPMENT NECESSARY TO COMPLETE THE ELECTRICAL WORK.
<br /> TEMP TEMPORARY CORRECT OPERATION OF EQUIPMENT, RESPONSE OF SENSORS,
<br /> TYP TYPICAL AND PROPER EXECUTION OF HVAC CONTROL AND LIGHTING SITE EXAMINATION
<br /> COORDINATE INSTALLATION OF CARBON MONOXIDE(CO)DETECTOR SEQUENCES; INCLUDING BUT NOT LIMITED TO,AIR MOVEMENT, THE ELECTRICAL CONTRACTOR SHALL THOROUGHLY EXAMINE ALL AREAS
<br /> UNO UNLESS NOTED OTHERWISE DEVICE(S)AND LOW VOLTAGE WIRING WITH STARBUCKS SECURITY TEMPERATURE,SOUND,AND CONTROL RESPONSE. PROVIDE ANY WHERE EQUIPMENT,CONDUIT,AND WIRING WILL BE INSTALLED AND WILL
<br /> VENDOR FOR NEW STORES, RELOCATIONS AND MAJOR RENOVATIONS, IF ENERGY MANAGEMENT SYSTEM (EMS) SECURITY ACCESS, HARDWARE, SOFTWARE,OR OTHER SUPPORT REPORT ANY CONDITION THAT, IN HIS OPINION, PREVENTS THE PROPER
<br /> WH WATER HEATER IN VENDOR SCOPE. VENDOR TO PROVIDE AND INSTALL DEVICE(S) IN BOH AS NEEDED FOR THE STARBUCKS CXA TO EFFICIENTLY WITNESS INSTALLATION OF THE ELECTRICAL WORK.
<br /> WP WEATHER PROOF AND FOH(AS APPLICABLE PER STARBUCKS STANDARDS). AND DOCUMENT ALL EQUIPMENT TESTING.STARBUCKS CXA WILL LO
<br /> THE GENERAL CONTRACTOR SHALL CONTACT AND COORDINATE RECORD THE EQUIPMENT OPERATION AND RESPONSE TO TESTING r
<br /> INSTALLATION OF<INSERT LCP PRODUCT>AND<INSERT EMS SYSTEM> STANDARDS
<br /> WITH EMS INSTALLER. PRIOR TO LAST WEEK OF CONSTRUCTION. SEQUENCES AND PREPARE A LIST OF ANY DEFICIENCIES EQUIPMENT AND MATERIALS SHALL CONFORM WITH APPROPRIATE U) CV
<br /> DISCLOSED BY THE FUNCTIONAL PERFORMANCE TESTS FOR Q Ln
<br /> FURNISH AND INSTALL TEMPORARY THERMOSTATS AND SENSORS,AND PROVISIONS OF CSA, ULC,NEC,ASTM, UL, E7L, NEMA,ANSI,AS APPLICABLE
<br /> FIRE ALARM SYSTEM NOTES ROUTE INATEWITHELE ELECTRICAL).
<br /> THROUGH EC PROVIDED CONDUITS NOT
<br /> TO, THE CONTRACTOR. EQUIPMENT INCLUDES,BUT IS TO EACH INDIVIDUAL UNIT OR ASSEMBLY.
<br /> (COORDINATE WITH ELECTRICAL). NOT LIMITED TO,AIR HANDLING UNITS, ROOFTOP AND SPLIT TYPE, W
<br /> CONDENSING UNITS, EXHAUST FANS, LIGHTING CONTROLS, ETC. CODES T m Q
<br /> IF STARBUCKS IS REQUIRED TO PROVIDE A FIRE ALARM AND/OR FIRE FURNISH AND INSTALL RACEWAYS WITH PULL STRINGS AND JUNCTION DELIVERABLES: PROVIDE COMPLETED COPIES OF ALL START UP ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH ALL 1 0)
<br /> ALARM MONITORING AND/OR PHONE LINES FOR A FIRE ALARM,AS REPORTS, FILLED OUT ON THE MANUFACTURER'S FORMS,TO THE U
<br /> BOXES FOR THERMOSTAT(S)AND SENSOR(S). APPLICABLE PROVINCIAL AND LOCAL CODES AND ORDINANCES. IN CASE OF �x
<br /> SPECIFIED IN THE LEASE AGREEMENT,THE CONTRACTOR IS TO NOTIFY STARBUCKS CXA. CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS AND THE CODES, W
<br /> GNOC IMMEDIATELY THAT FIRE ALARM LINES ARE NEEDED. STARBUCKS SET RESTROOM OCCUPANCY SENSOR TO 15 MINUTE'ON' DURATION IN THE HIGHEST STANDARD SHALL APPLY. ELECTRICAL CONTRACTOR SHALL Z
<br /> H. CONTRACTOR IS RESPONSIBLE FOR CORRECTING ANY ISSUES OR
<br /> PREFERRED FIRE ALARM SERVICE PROVIDER,STANLEY, IS BE SINGLE OCCUPANT RESTROOM AND20 M Q O
<br /> FI
<br /> CONTACTED BY THE CONSTRUCTION MANAGER TO INSTALL FIRE ALARM MULTI-OCCUPANT RESTROOM UNLESSS JURISDICTIDICTI ON'DURATION IN SATISFY CODE REQUIREMENTS AS A MINIMUM STANDARD WITHOUT ANY ON REQUIREMENTS DEFICIENCIES DISCLOSED DURING THE FUNCTIONAL PERFORMANCE EXTRA COST TO STARBUCKS.
<br /> TESTING PROCESS. CORRECTIONS SHOULD BE MADE IN A TIMELY
<br /> STATE OTHERWISE.
<br /> PANEL AND/OR MONITORING SERVICE AS REQUIRED. MANNER WITHOUT DISRUPTION TO THE SYSTEM AND < W Y
<br /> CONSTRUCTION SCHEDULE. PERMITS AND FEES US
<br /> U
<br /> COORDINATE WITH DRAWINGS AND LCP VENDOR FOR DEVICE THE ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, O W
<br /> LOCATIONS. VENDOR SHALL COMMISSION CONTROLS. I. CONTRACTOR SHALL BE READILY AVAILABLE FOR ANY RE-TESTING FEES,AND INSPECTIONS NECESSARY TO COMPLETE THE ELECTRICAL WORK. LU W 0
<br /> THE
<br /> TOR IS TO
<br /> PLETE FINAL
<br /> AFTEREDATA RACK AND CNETWORK INSTIALLATION. THE GENERAL IN EQUIPMENT DEEMED NECESSARY BY STARBUCKS CXA DURING WARRANTY EELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY WARRANT ALL Z = Q Q
<br /> INSTALLATION VERIFICATION AND FUNCTIONAL PERFORMANCE
<br /> CONTRACTOR IS TO CONTACT LCP VENDOR TO VERIFY SYSTEM TESTING.CONTRACTOR IS RESPONSIBLE FOR CORRECTING ANY WORK TO BE FREE OF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A H-
<br /> ISSUES OR DEFICIENCIES FOUND IN THE SYSTEM DURING ANY AND
<br /> OPERATION AND TROUBLESHOOT IF REQUIRED. PERIOD OF ONE(1)YEAR FROM THE DATE OF FINAL ACCEPTANCE BY U U U Z D
<br /> ALL RE-TESTING.CORRECTIONS SHOULD MADE A TIMELY W W a) O Q
<br /> MANNER WITHOUT DISRUPTION TO THE SYSTEM ANDD STARBUCKS AND WILL REPAIR OR REPLACE ANY DEFECTIVE WORK ' -a
<br /> CONSTRUCTION SCHEDULE. DELIVERABLES: FINAL BALANCE PROMPTLY AND WITHOUT CHARGE AND RESTORE ANY THER EXISTING 0 0
<br /> WORK DAMAGED IN THE COURSE OF REPAIRING DEFECT VE MATERIALS AND a X 00 0� O
<br /> CONTROLS AND OPERATION REPORT, DEFICIENCIES LIST NOTING CORRECTIVE ACTIONS WORKMANSHIP. 0- D- -t LL 0'
<br /> PERFORMED BY CONTRACTOR IN RESPONSE TO INSTALLATION
<br /> VERIFICATION AND FUNCTIONAL PERFORMANCE TEST RESULTS. LEED STORE #: 10183
<br /> THE GENERAL CONTRACTOR SHALL CONTACT AND COORDINATE J. CONSTRUCTION AND POST CONSTRUCTION TESTING:ADDITIONAL ALL WORK, MATERIALS AND EQUIPMENT SHALL MEET LEED REQUIREMENTS&
<br /> INSTALLATION OF LIGHTING CONTROL PANEL WITH"LUTRON" TESTING MAY BE REQUIRED BY LEED AND OTHER PROCESSES THAT CODE. IN CASE OF CONFLICT,THE HIGHER STANDARD SHALL APPLY. PROJECT#: 27237-038
<br /> PRIOR TO THE LAST WEEK OF CONSTRUCTION. MAY OCCUR OUT OF SEQUENCE WITH COMMISSIONING SERVICE. CASEWORK CONCEPT:
<br /> CONTRACTOR SHALL CONDUCT, DOCUMENT, SUPPORT AND
<br /> FURNISH AND INSTALL RACEWAYS WITH PULL STRINGS AND JUNCTION BOXES SCHEDULE THIS TESTING AS DIRECTED BY STARBUCKS CXA. ISSUE DATE:
<br /> FOR THERMOSTAT(S)AND SENSOR(S). LANDLORD REQUIREMENTS DESIGN MANAGER:
<br /> SET RESTROOM OCCUPANCY SENSOR TO 15 MINUTE'ON' DURATION IN SINGLE LEED®AP:
<br /> OCCUPANT RESTROOM AND TO 20 MINUTE'ONDURATION IN MULTI-OCCUPANT PROGRAM MANAGER: HT
<br /> RESTROOM UNLESS JUSRISDICTION REQUIREMENTS STATE OTHERWISE. PRIOR 7BID: THE CONTRACTOR SHALL COORDINATE WITH LANDLORD I CHECKED BY: TG
<br /> WIRELESS NETWORK NOTES BUILDINGG OWNER FOR ANY CONSTRUCTION REQUIREMENTS/
<br /> COORDINATE WITH DRAWINGS AND LCP VENDOR FOR DEVICE LOCATIONS. SPECIFICATONS. IF LANDLORD/BUILDING OWNER DOES HAVE
<br /> VENDOR SHALL COMMISSION CONTROLS. REQUIREMENTS, CONTRACTOR SHALL BECOME COMPLETELY FAMILIAR Revision Schedule
<br /> CABLING FOR INTERNET SERVICE SHALL BE FURNISHED AND INSTALLED BY WITH REQUIREMENTS/SPECIFICATIONS AND ADHERE TO THEM. WHERE
<br /> THE GENERAL CONTRACTOR IS TO COMPLETE FINAL CONNECTION AFTER DATA THE VENDOR FOR FIBER OR BROADBAND CONNECTIONS. T7 AND ETHERNET LANDLORD/BUILDING OWNER REQUIREMENTS ARE MORE STRINGENT Rev Date I By Description
<br /> RACK AND NETWORK INSTALLATION. THE GENERAL CONTRACTOR 13 TO EXTENSION CABLING IS PROVIDED BY THE STARBUCKS(TELEPHONE/ THAN SHOWN IN THESE PLANS(IN THE OPINION OF THE ENGINEER). 06-05-18 SS PERMIT SET
<br /> CONTACT LCP VENDOR TO VERIFY SYSTEM OPERATION AND TROUBLESHOOT IF NETWORK)CABLING VENDOR. COORDINATE WITH STARBUCKS. LANDLORD/BUILDING OWNER REQUIREMENTS SHALL GOVERN.
<br /> REQUIRED.
<br /> 1
<br /> MUSIC SYSTEM NOTES 3
<br /> MOUNT OWNER FURNISHED SPEAKERS WHERE SHOWN ON INTERIOR SHEET TITLE:
<br /> REFLECTED CEILING PLANS AND IN COORDINATION WITH ALL PLANS, ELECTRICAL NOTES
<br /> DETAILS AND MANUFACTURER'S INSTALLATION REQUIREMENTS. INSTALL
<br /> AND CONNECT OWNER FURNISHED WIRING SYSTEM BETWEEN ALL
<br /> SPEAKERS AND THE OWNER PROVIDED MUSIC SYSTEM.
<br /> SCALE:AS SHOWN
<br /> SHEET NUMBER:
<br /> E-0001