Laserfiche WebLink
11( 'I <br /> i <br /> Line Leak Detector Test Data Sheet <br /> Station# Arco 6080 Date 1/22/2019 20 <br /> Address 85 E Louise Ave. Lathrop, CA 95330 <br /> Test Information <br /> 1 2 3 4 g <br /> Product 87 91 <br /> DSL <br /> Manufacturer VR VR VR <br /> Model 848480 848480 <br /> 848480 <br /> Full Operating Pressure (psi) 34 34 32 <br /> Line Bleed Back(ml) NA NA NA <br /> Trip Time(sec) NA NA <br /> NA <br /> Metering Pressure (psi) NA NA NA <br /> F/E Holding Pressure(psi) 32 32 30 <br /> Test Leak Rate(ml/min)(gph) 189ML 189ML 189ML <br /> PASS or FAIL Pass Pass Pass <br /> Comments: <br /> This letter certifies that the annual leak detector tests were peri'ormcd at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass:Tail is detennined using a low <br /> (]ow threshold trip rate ol'3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler Ryan Inc. <br /> Technician David Ouse Lic#220793 <br /> Signature <br />