Laserfiche WebLink
RECEIVED <br /> FEB Q 7 2019. <br /> ENVIRONMENTAL HEALTH <br /> HOW TO LOCATE THE POSITION OF THE BERARTMENIT <br /> 71SO AT 95%TANK CAPACITY Measuring Stick <br /> The length of the upper tube and the placement of - - -- - <br /> the 71 SO valve body determine the shut-off point. } <br /> Fallowing the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all (, <br /> cases,the upper tube length must be a minimum of d, <br /> 6-112"plus the length of the riser pipe. All length - <br /> measurements are in inches. Riser Pipe <br /> with Face (A) <br /> INSTRUCTIONS Seal Adaptor To Tank <br /> 1.) Find tank capacity(in gallons)from tank Top(L17.) To Tank <br /> �i��� Bottom <br /> calibration chart provided by tank manufacturer. <br /> btriz q 2.)Calculate 95%of capacity. -------• . 'Ll <br /> 6-112" <br /> 3.)Locate the 95%volume number on the tank <br /> calibration chart. t <br /> tv t !y 4.)Find the dipstick number(X)which corresponds Figure 1 <br /> '- to the 95% tank volume. And, find the dipstick <br /> Sit number(Y)which corresponds to the EXAMPLE <br /> 100%volume. 1.) For an Owens-Corning Model G-3 Fiberglass® <br /> Tank Calibration Chart: <br /> 5.)Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal.. nominal 9,403 gal. <br /> 1Z'3S diameter(Y)to find the upper tube reference NOTE: Use actual capacity only <br /> number(Z). <br /> = lfl 35 (Y)- (X)= (Z) 2.)95%of actual tank capacity=0.95 x <br /> 6.)Subtract 2"from(Z)to find the upper tube depth 9403 gal. =8933 gal. <br /> P. 3.)The closest number which is less than 8933 gal. <br /> (Z)-2"=C Is 8910 gal. Choosing the closest number less <br /> than 95%of actual capacity ensures that the <br /> 7C less than 6-112"? initial shutoff will occur when the tank is no more <br /> than 95%full. <br /> NO 1 Upper tube length is C plus the distance/ from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe to the inside, top corresponds to a dipstick measurement of 82". <br /> lip of the storage(A). <br /> 5.) Dipstick number(X)= 82" <br /> Upper Tube Length = C+ (A) Tank diameter(Y)=92" <br /> �� <br /> (Y)-(X)= (Z) (92 "-82"= 10") <br /> YES Upper tube length is 6-112"plus the riser (Z)= 10" <br /> pipe measurement(A). <br /> 7.) (Z)-2" =C (10"-2"= 8") <br /> Upper Tube Length =6-112" +(A) C=8" <br /> NOTE: You must find the actual tank capacity 7.) Is 8"less than 6-112"? <br /> number that correlates to the 6-112"+(A) depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside,top lip of the storage <br /> tank and obtain measurement(A). <br /> D Registered T.M -Owens Corning Fiberglass Corporation Upper tube length =C+ (A) <br /> 64 <br />