t2 Sl�_ <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71 SO AT 95%TANK CAPACITY Measuring Stick <br /> The length of the upper tube and the placement of <br /> the 71 SO valve body determine the shut-off point. <br /> Fallowing the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all <br /> cases,the upper tube length must be a minimum of r <br /> 6-1/2"plus the length of the riser pipe. All length <br /> measurements are in inches. Riser Pipe i fi <br /> with Face (A) <br /> INSTRUCTIONS Seal Adaptor To Tank <br /> (8) <br /> XO,'t.S-i 1.)Find tank capacity(in gallons)from tank Top(LD.) To Tank <br /> calibration chart provided by tank manufacturer. I, Bottom <br /> C o <br /> (1yl 2.)Calculate 95%0#capacity. ---�----- --- ^� ' -- <br /> 6-1/2" <br /> �Ob ,17 3)Locate the 95%volume number on the tank <br /> calibration <br /> Figure 1 <br /> 4.)Find the dipstick number(X)which corresponds <br /> to the 95% tank volume. And, find the dipstick <br /> (Yu' number(Y)which corresponds to the EXAMPLE <br /> 100%volume. 1.) For an Owens-Coming Model G-3 FiberglassV <br /> Tank Calibration Chart: <br /> 5.)Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gat., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube reference NOTE: Use actual capacity only <br /> �( t number(Z). <br /> .. (Y)- (X)_ (Z) 2.)95% of actual tank capacity=0.95 x <br /> 9403 gal. =8933 gal. <br /> 6.)Subtract 2 from(Z)to find the upper tube depth <br /> (C). 3.)The closest number which is less than 8933 gal. <br /> (Z)-2"=C Is 8910 gal. Choosing the closest number less <br /> than 95% of actual capacity ensures that the <br /> 7.)Is C less than 6-1/2"? initial shutoff will occur when the tank is no more <br /> .-� <br /> NO Upper tube length is C plus the distance than 95%full. <br /> from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe to the inside, top corresponds to a dipstick measurement of 82". <br /> lip of the storage(A). <br /> 5.) Dipstick number(X)=82" <br /> Upper Tube Length =C + (A) Tank diameter(Y)= 92" <br /> (Y)-(X)= (Z) (92 "-82"= 10") <br /> YES Upper tube length is 6-112"plus the riser (Z)= 10" <br /> pipe measurement (A). <br /> 7.) (Z)-2"=C (10"-2"= 8") <br /> Upper Tube Length =6-1/2"+(A) C=8" <br /> NOTE: You must find the actual tank capacity 7.) Is 8"less than 6-1/2"? <br /> number that correlates to the 6-1/2" + (A) depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside, top lip of the storage <br /> tank and obtain measurement(A). <br /> rJ Registered T.M.-Owens Corning Fiberglass Corporation Upper tube length = C+(A) <br /> 64 <br />