Laserfiche WebLink
FROM : TAIT & ASSOCIATES — Saci :nto FAX NO. 9166352606 Jan. 02 2002 11:07RM P11 <br /> TECHNICAL SPECIFICATIONS <br /> 0 Designed to handle <br /> ...100% gasoline, methanol, ethanol <br /> Any combination of the above l ,f <br /> ...100% diesel <br /> r.. ,. <br /> ...Up to 15% MTBE <br /> • For use with any UL listed pumps: 1/3 h,p., 3/4 <br /> h.p., and 1-1/2 h.p. - 20-50 psi, volume to 90 GPM <br /> 0 Certified to handle 10 feet of head pressure <br /> Combination Iine check/pressure relief, prevents <br /> drainback into the tank <br /> • Untque upper cylinder piston functions without a <br /> pressure relief(patent pending) <br /> • Latest generation UL approved "Super Viton" for 0-rings <br /> a Can be installed in any position <br /> • Tamper-proof bolts accommodate wire seal to prevent <br /> tampering <br /> • Hardened 17-4 stainless steel metering pin and poppet <br /> • More resilient line seal for a wide variety of <br /> submersible pumps <br /> • For installation in 2 inch NPT threads <br /> Leak detector is nickel-plated, schedule 40 cast iron construction <br /> i <br /> • UL listed and EPA certified (3 GPH ® 10 psi) for Iine <br /> systems up to 130 gallons <br /> r j <br /> • Compatible with thermal contraction accumulator for _;. _ <br /> extreme temperatue differentials <br /> Yi <br /> 0 Vent line must be unobstructed, leak-proof, and a x ! <br /> connected to a zero pressure port <br /> WARRANTY INFORMATION <br /> The LD-2000 mechanism is fully guaranteed to see a leak of 3 GFH ® 10 psi for a period of 18 months <br /> after date of installation. Warranty card and installation instructions included in pack <br />