Laserfiche WebLink
(3) Leak Detection: Documented daily inspection. <br />(k) Tank Assessment: <br />(1) Tank Configuration <br />Waste Oil Tank: <br />Tank Configuration: Horizontal, rectangular, double chamber <br />Material of Construction: <br />Primary Inner Tank: A-36 Carbon steel <br />Secondary Containment: High Density Polyethylene <br />Outer Shell: Reinforced Concrete <br />Gross Capacity: 1,000 Gallons <br />Used Coolant Tank: <br />Tank Configuration: Circular vertical <br />Material of Construction: PVC <br />Gross Capacity: 200 gallons <br />(2) Design Standards: <br />UL 142 Standard for Steel Aboveground Tanks for Flammable and Combustible <br />Liquids <br />UL -2085 Two Hour Furnace Test for Insulated and Protected Tanks <br />NFPA 30 Flammable and Combustible Liquids Code <br />NFPA 30A Code for Motor Fuel Dispensing Facilities and Repair Garages 2008 <br />SAE J517 Standard for Hydraulic Hoses <br />(A) Material of Construction: <br />Waste Oil Tank: <br />Primary Inner Tank: A-36 Carbon steel <br />Secondary Containment: High Density Polyethylene <br />Outer Shell: Reinforced Concrete <br />Used Coolant Tank: <br />Polyvinyl chloride <br />Ancillary Equipment: <br />Conveyance Hose: Gasoline Service Hose, 3/4" ID, <br />synthetic rubber composite. <br />