Laserfiche WebLink
0 <br />Flammability: 1 (slight) <br />Reactivity: 0 (minimal) <br />Stored waste liquids in the used coolant storage tank are not classified by OSHA <br />as combustible. <br />These liquids have the following HMIS Hazard Ratings� <br />Health: 2(moderabe) <br />Ftam/nabi|hy� 1 (slight) <br />Reactivity: U (minimal) <br />(3)Not Applicable: Tanks are not incontact with soil orwater. <br />(4) Protection from Traffic: <br />Both above ground tanks are protected by a row of 6" pipe/concrete bollards from <br />adjacent traffic lanes <br />(G)Design Cunmidenation& <br />(A) Tank Foundation <br />The Convault waste oil tank is supported by a 10" reinforced concrete slab. The <br />approximate weight of the tank and contents when full is 18,000 lb. The floor <br />area supporting the tank is 696 in~ The floor load is 25.9 psi. The concrete <br />specification for typical concrete slab is 3,000 pmi, therefore the concrete <br />foundation supporting this waste oil tank is sufficient to support this load. <br />The used coolant tank issupported bya1["reinforced concrete slab. The <br />approximate weight of the tank and contents when full is 2,314 lb. The floor area <br />supporting the tank is 1.385 in The floor load is 1.7 psi The concrete <br />specification for a typical concrete slab is 3,000 psi, therefore the concrete <br />foundation supporting this waste oil tank is sufficient to support this load. <br />(B) Not Applicable: Tank is not in a saturated zone or a seismic fault zone. <br />(C) Not Applicable: Installation is in USDA Climate Zone Ab. 25 -30F annual <br />minimum temperature. <br />(1) Weld Breaks: None <br />(2) Punctures: None <br />(3) Scrapes VfProtective Coatings: None <br />(4) Cracks: None <br />(5)Corrosion: None <br />