After final alignment and bolting, pump connections shall be tested for <br /> applied piping stresses by loosening the flange bolts. If any movement <br /> or opening of the joints is observed, piping shall be adjusted to proper <br /> fit. <br /> 11A-11. DRAWINGS AND DATA. Complete fabrication, assembly, foundation, <br /> and installation drawings, together with detailed specifications and <br /> data covering material used, parts, devices, and other accessories <br /> forming a part of the equipment furnished, shall be submitted. The data <br /> and specifications for each unit shall include, but shall not be limited <br /> to, the following: <br /> Pumps <br /> Name of manufacturer <br /> Type and model <br /> Rotative speed <br /> Size of suction nozzle <br /> Size of discharge nozzle <br /> Net weight of pump only <br /> Net weight with baseplate and coupling <br /> Complete performance curves showing capacity versus head, <br /> NPSH required, pump efficiency, and gpm. <br /> Data on shop painting <br /> Operating & Instruction Manuals <br /> Type of coupling <br /> Motors <br /> Name of manufacturer <br /> Type and Model <br /> Type of bearings and lubrication <br /> Rated size of motor, hp <br /> Temperature rating <br /> Full load rotative speed <br /> Net weight <br /> Efficiency at full , 3/4, and 1/2 load <br /> Full load current <br /> Locked rotor current <br /> Operating & Instruction Manuals <br /> (MARLEY FSSF ) <br /> (CONTRACT NO. 13) 11A-6 <br /> J <br />