Laserfiche WebLink
Fluid Switch <br /> PROJECT DATA SHEET No, REV. <br /> DATA SHEET NCTC Soil Flushing <br /> Syztn PAGE I OF l 0 <br /> REVISION$ PLANT BUILDING PREPARED BY THIS SHEET PART OF <br /> REV. APPROVAL OAT E Stockton, CA Black s Veatch 16A <br /> W.O. OR E.S.O. APPROVAL DATE <br /> EF <br /> AEOUISITION NO. PROCURED BY INSTALLED BY <br /> Equipment Number: FS 13-01 <br /> FUNCTION: Provide a closed contact to the Influent Pump controls <br /> when liquid is detected in the Influent 3" suction <br /> piping and an open contact when no liquid is detected <br /> in the 3" suction piping. <br /> DESCRIPTION: Stainless steel fluid switch body with teflon sensor <br /> sheath and integral electronics energizes the output <br /> relay when liquid is in the line. NEMA 4X housing . <br /> RATING: Power Supply: 120VAC <br /> Output Contacts : DPDT, 10 AMPS @ 120VAC <br /> Operating Temp. : Minimum -20OF Maximum 200OF <br /> Operating Pressure: 200 psig <br /> MOUNTING: Thread-O-Let, 1 1/21m NPT Minimum <br /> flanged, 2"/150 # Minimum <br /> MANUFACTURER/ <br /> CATALOG NUMBER: Delta Controls Corp. <br /> 633-D-N4X-1 1/2" NPT <br /> REMARKS: <br /> Furnish the following manufacturer's data In quantities indicated: NUNER OF COPIES <br /> W Bids <br /> Approval Certified <br /> 1. Outline dimensional drawln s <br /> 2. Performance date <br /> 3. Weight of eaullument <br /> A. Descriptive literature <br /> 5. Descri tive literature <br /> 'InfOmtion to be supplied by equipaant manufacturer. <br />