BAY AEA <br /> rix <br /> 8 :.NTi7K,S <br /> 4 .0 CONCLUSIONS AND RECOMMENDATIONS <br /> Limitations : This inspection was conducted in accordance with generally accepted industrial <br /> standards and represents site conditions during the time of the visit. The report is intended for <br /> use by Conti and may not be used by others without written consent. The inspection did not <br /> include review of design drawings or weld inspection reports . If external UTs were performed, <br /> they are limited in that all internal pitting cannot be discovered . As such the limits of this report <br /> are as an overall survey of the tank and piping and this report does not serve as a guaranty of <br /> future system performance . Due care has been taken to verify and confirm the accuracy of this <br /> report. <br /> The inspection focuses on a failure mode which can be determined by visual and interstice <br /> inspections and may not identify modes of failure such as stress corrosion cracking, hydrogen <br /> embrittlement, and micro effects of metal flaws in steel manufacturing which would require a <br /> more extensive non-destructive and destructive testing. A safety factor is used to accommodate <br /> these unknowns as is typical in engineering analysis . <br /> Findings and Recommendations : After reviewing site conditions presented by BATC, it appears <br /> that tank 1 is in operational condition. It is required that in the next six months the following <br /> required upgrades be implemented . <br /> 1 . ) Ensure manway lid is not stuck to the tank . <br /> It is recommended that the following items be completed to increase the useful life of the tanks . <br /> 1 . ) Place NFPA placards on the tank. <br /> 2. ) Anchor the tank. <br /> 3 . ) Repair failing coatings; Re-paint. <br /> 4. ) Address overfill alarms by installing overfill alarm or using active maintenance . <br /> 5 . ) Install grounding <br /> 6 .) Implement monthly inspection of interstice . <br /> Rudolph Bowman, Tr P . E . <br /> Printed Name of SP-001 Inspector <br /> 1 2/ 06 / 19 <br /> Signature of API/ SP-001 Inspector Date Certified <br /> AST- 40310 November 19 2020 <br /> STI SP-001 Expiration Date of Registration <br /> 60073 Tuly 31 , 2021 <br /> API 653 Inspector. Expiration Date of Registration <br /> 4 <br /> BAY AREA SPANK & COATINGS , LLC 2115 E . 27TI3 ST VANCOUVER , AVA 98661 <br /> OFFICE 360 . 314 . 2448 FAX 360 . 314 . 2691 <br />