Laserfiche WebLink
op ri <br /> oloc <br /> ty <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SITE NAME: SAFEWAY 2600 2600 DATE: 02/03/2003 WORK ORDER 2225356 <br /> SITE ADDRESS: 1987 WEST 11TH TRACY CA 95376 <br /> REASON FOR TEST: SB-989 6-Month Groundwater Level(" from grade): <br /> TANK INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Depth Start Initial Finish Final Pass/ <br /> Tan Product Tank Size Material Manufacturer Test Method Time Level Time Result Fail <br /> 1 REG UNLEAD 20073 120 DW STEEL <br /> 2 PLUS 10037 120 DW STEEL <br /> 3 PREMIUM 10037 120 DW STEEL <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> Comments: <br /> LINE INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Len. Volume Start Initial Finish Final Pass/ <br /> Tan Product feet Material Manufacturer (gallons) Test Method Time Level Time Result Fail <br /> 1 Reg DW Flex Western Fiberglass Pressure 2:02 5 psi 2:20 0 psi FAIL <br /> 2 Plus DW Flex Western Fiberglass Pressure 12:23 5 psi 1:23 5 psi PASS <br /> 3 Prem DW Flex Western Fiberglass Pressure 1:35 5 psi 235 5 psi PASS <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> LLery small leak in reg line.Probably in dispensers or sump. <br />