Laserfiche WebLink
_ Test Date: 02/03/2003 <br /> PP 7bnkncdcPmy Work Order: 2225356 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Type Tank or Disp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material (") (") Time Level Change Time Result Fail <br /> Dispenser Sump 1/2 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 12:06 18 .083 12:21 1.995 Fail <br /> Dispenser Sump 3/4 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 12:06 18 .000145 12:21 .003 Pass <br /> Dispenser Sump 5/6 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 1:35 18 .00033 1:50 .007 Pass <br /> Dispenser Sump 7/8 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 12:55 18 .00003 1:10 .000 Pass <br /> Dispenser Sump 9/10 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 258 18 .0867 313 2.064 Fail <br /> Dispenser Sump 11112 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 2:57 18 .0622 3:12 1.482 Fail <br /> Dispenser Sump 13/14 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 3:40 18 .000055 3:55 .0013 Pass <br /> Dispenser Sump 15/16 Western Fiberglass Fiberglass 42 30 Hydrostatic-VPLT 3:40 18 .0000 355 .000 Pass <br /> Comments: Dispensers seem to be leaking at the comers/edges of the sump.Leak rate slows down as water level drops all the way to the bottom. <br />