Laserfiche WebLink
PEURP1200-17 <br />LIST OVERFILL EQUIPMENT INSPECTION <br />AUTOMATIC SHUTOFF DEVICE AND BALL FLOAT <br />Facility Name: Owner: <br />Address: Address: <br />City, State, Zip Code: City, State, Zip Code: <br />Facility I.D. #: Phone #: <br />Testing Company: Phone #: Date: <br />This data sheet is for inspecting automatic shutoff devices and ball float valves. See PEI/RP1200 Section 7 for inspection procedures. <br />Product Grade <br />Tank Number <br />Tank Volume, gallons <br />Tank Diameter, inches <br />Overfill Prevention Device Brand <br />Type <br />❑ Automatic <br />❑ Automatic <br />❑ Automatic <br />❑ Automatic <br />❑ Automatic <br />❑ Automatic <br />Shutoff Device <br />Shutoff Device <br />Shutoff Device <br />Shutoff Device <br />Shutoff Device <br />Shutoff Device <br />❑ Ball Float <br />❑ Ball Float <br />❑ Ball Float <br />❑ Ball Float <br />❑ Ball Float <br />❑ Ball Float <br />Valve <br />Valve <br />Valve <br />Valve <br />Valve <br />Valve <br />AUTOMATIC SHUTOFF DEVICE INSPECTION <br />1. Drop tube removed from tank? <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />2.Drop tube and float mecha- <br />[]Yes ❑ No <br />[]Yes ❑ No <br />[]Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />nisms free of debris? <br />3. Float moves freely without <br />binding and poppet moves into <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />[]Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />flow path? <br />4.Bypass valve in the drop tube <br />❑ yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />open and free of blockage (if <br />❑ Not Present <br />❑ Not Present <br />❑ Not Present <br />❑ Not Present <br />❑ Not Present <br />❑ Not Present <br />present)? <br />5.Flapper adjusted to shut off <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes D No <br />[--]Yes ❑ No <br />❑ Yes ❑ No <br />flow at 95% capacity?* <br />A "No" to any item in Lines 1-5 indicates a test failure. <br />BALL FLOAT VALVE INSPECTION** <br />1.Tank top fittings vapor- tight <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />and leak -free? <br />2. Ball float cage free of debris? <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />[]Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />3.13all free of holes and cracks <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />and moves freely in cage? <br />4.Vent hole in pipe open and <br />❑ Yes ❑ No <br />[]Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />near top of tank? <br />5.Ball float pipe proper <br />length to restrict flow at 90% <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />capacity?*** <br />A "No" to any item in Lines 1-5 indicates a test failure. <br />Test Results <br />❑ Pass ❑ Fall <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Comments: <br />* Use manufacturer's suggested procedure for determining if automatic shutoff device will shut off flow at 95% capacity. <br />** If a ball float is found to fail the inspection, another method of overfill must be used. <br />*** Use manufacturer's suggested procedure for determining if flow restriction device will restrict flow at 90% capacity. <br />Tester's Name (print) Tester's Signature <br />0 pei.org <br />