Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: ARCO #02186 <br /> Tank #: 2 Test Date: 1/15/97 <br /> Product: Unleaded Regular Work#: 50276 <br /> Test Method: System 4000 7 Test Method: R.J.FTA <br /> Capacity: 10000 Manufacturer: Vaporless <br /> Diameter(in): 95 L/D Model: LD2000 <br /> Product Level(in): 74 L/D Serial#: <br /> Liquid Volume(Gals): 8295 Line Drain Back(ml): 280 <br /> Liquid Percent(%): 83.0% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 24 <br /> Coef. of Expansion: 0.000667 Metering Pressure(psi): 12 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.2 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 60.39 <br /> Head Pressure(psi): 2.0 <br /> Test Start Time: 8:40:00 AM Test Method: TEI LT-3 <br /> Test End Time: 11:10:00 AM Pump Brand: Red Jacket <br /> Test Rate(gph): -0.031 System Type: Pressure <br /> Test Result: PASS Line Pressure(psi): 50 <br /> Line Start Time: 10:26:00 AM <br /> Test Method: ULLAGE Line End Time: 10:41:00 AM <br /> UllageVolume(gals.): 1705 Line Start Level: 290 <br /> Ullage Test Time: 11:50:00 AM Line End Level: 260 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): -0.03 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 3 <br />