Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: ARCO #02186 <br /> Tank #: 3 Test Date: 1/15/97 <br /> Product: Unleaded Super Work#: 50276 <br /> Test Method: System 4000 Test Method: R.J. FTA <br /> Capacity: 10000 Manufacturer: Vaporless <br /> Diameter(in): 96 L/D Model: LD2000 <br /> Product Level(in): 79 L/D Serial#: <br /> Liquid Volume(Gals): 8829 Line Drain Back(ml): 219 <br /> Liquid Percent(%): 88.3% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 24 <br /> Coef. of Expansion: 0.000665 Metering Pressure(psi): 12 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.4 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 59.55 <br /> Head Pressure(psi): 2.1 <br /> Test Start Time: 8:40:00 AM Test Method TEI LT-3 <br /> Test End Time: 11:10:00 AM Pump Brand: Red Jacket <br /> Test Rate(gph): -0.047 System Type: Pressure <br /> Test Result: PASS <br /> Line Pressure(psi): 50 <br /> ULLAGE TEST RESULT ' " Line Start Time: 10:45:00 AM <br /> Test Method: ULLAGE Line End Time: 11:00:00 AM <br /> UllageVolume(gals.): 1171 Line Start Level: 230 <br /> Ullage Test Time: 12:00:00 PM Line End Level: 210 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): -0.02 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 7 <br /> 4 <br />