MAY 2 6 2016 <br /> SWRCB,January 2002 Page_3 of 7- <br /> 5. SECONDARY PIPE TESTINGS�L. ,. .��.. <br /> Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ®Pressure ❑Vacuum ❑ Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used:0--15 PSI GAUGES Equipment Resolution: .5% <br /> gym M-121, <br /> Piping Run#87(2) <br /> Piping Run#87(1) SYPHON Piping Run# Piping Run#91 <br /> Piping Material: FIBERGLASS FIBERGLASS FIBERGLASS <br /> Piping Manufacturer: A.O.SMITH A.O.SMITH A.O.SMITH <br /> Piping Diameter: 2"X 3" 2"X 3" 2"X 3" <br /> Length of Piping Run: 125' 25' 150' <br /> Product Stored: 87 87 91 <br /> Method and location of TEST BOOT/ TEST BOOT 1 TEST BOOT I <br /> piping-run isolation: STP SUMP STP SUMP STP SUMP <br /> Wait time between applying <br /> pressure/vacuum/water and 10 MIN 10 MIN 10 MIN <br /> starting test: <br /> Test Start Time: 11:00 11:00 11:00 <br /> Initial Reading(Rj): 5.0 PSI 5.0 PSI 5.0 PSI <br /> Test End Time: 12:00 12:00 12:00 <br /> Final Reading(RF): 5.0 PSI 0.0 PSI 5.0 PSI <br /> Test Duration: 1 HR 1 HR 1 HR <br /> Change in Reading(RF-Ri): 0 PSI 5.0 PSI 0 PSI <br /> Pass/Fail Threshold or NO LOSS NO LOSS NO LOSS NO LOSS <br /> Criteria: <br /> Test Result: ® Pass ❑Fail ❑Pass ® Fail ®Pass ❑Fail ❑Pass ❑Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 87(2)SYPHON LINE FAILED. LEAKS CONFIRMED AT 87(2)STP SUMP ON SECONDARY FIBERGLASS LINE. <br /> THERE IS A CRACK 1 FRACTURE <br />