Laserfiche WebLink
SMITH <br /> INSTALLING UL LISTED RED THREAD II <br /> PRODUCT PIPE LINES (continued) <br /> SUCT M Pur. <br /> DWAUAT1D11a <br /> .U..LD <br /> DRNE <br /> TTHREADRED�ED = Kmeu MR MIIR Amount of sand <br /> ADAPT" CONWCT M Burial or Pea Gravel above <br /> � <br /> Size Surface Cortion Depth the lop of"pipe <br /> si- 2" Unpaved 17" 12" <br /> e1eALlATq S eeTAu.Ai�Diu Paved,min.4"asphalt .12" - 8" . <br /> Paved,min_.4"concrete 9" 5" <br /> 3" Unpaved 20" 14" <br /> Paved,min.4"asphalt 13 9" <br /> Paved,min.4"concrete 11" 7" <br /> RED THREAD I QALR.tx�x.E ■I vPA�TO 4" Unpaved 20" 14" <br /> THR ADAPTER CONNECTION GALVAMDMD Paved,min.4"asphalt 14" 10" <br /> SWING Paved,min.4"concrete 1 11" 7" <br /> AS9E1lU'Al <br /> TYPICAL ISLAND PIPING <br /> PLUMBING —To make installation easier and to Minimum burial depths shown it the above burial table are <br /> conserve adhesive,all measuring. cutting,and tapering acceptable if, and only if,the ditch width is 2.5 feet or less; <br /> should be done first.Then proceed with the bonding the paved surfaces extend at least 2 feet on either side of <br /> operation.To make sure measurements are right, the ditch, the fill material is clean sand or 1/8" to 1/2" pea <br /> assemble the entire piping system "dry"(without adhesive) gravel and 6" of the fill material is placed under the pipe as <br /> before bonding.Where accuracy is important,"dry' bedding material. <br /> assembly is a must. For close tolerance piping refer to Remaining backfill above Sand or Pea Gravel amounts as <br /> Smith Fiberglass Installation Manual No. 9474. shown in the last column of the burial table can be native <br /> FLEXIBLE HOSE CONNECTIONS— Flexible hose soil if desired, <br /> connections can be installed in product and vent lines at If burial conditions other than those discussed above exist, <br /> the point where they leave the tank. On suction pump contact Smith Fiberglass Products. <br /> installation they can be put in just before the pump riser. <br /> Use of flexible connections can prevent breaking of lines REPAIRING — On rare occasions it may be necessary to <br /> or fittings where settlement might cause tank movement,or repair a damaged section of RED THREAD II pipe.Where <br /> where expansion and contraction might cause movement damage is in the form of a puncture,the pipe can be <br /> of the pipe. repaired using a patch made from the pipe itself. If a <br /> The drawings above of typical island piping indicate how considerable length of pipe is involved, it is best to replace <br /> it with a new section of pipe.Complete information for <br /> connections can be made using standard RED THREAD making repairs is included in the Smith Fiberglass UL <br /> II adapters. Installation Instructions Manual No. 1055. <br /> BURIAL— Minimum acceptable burial depths are given <br /> in this section. In some cases greater depths may be For industry reference, see API Publication 1615 <br /> required by the authority having jurisdiction or by local "Installation of Underground Petroleum Storage Systems" <br /> codes. and PEVRP100-86 "Recommended Practices for <br /> The maximum allowable burial depth is 24 feet for burial in Installation of Underground Liquid Storage Systems" <br /> moderately compacted soils which do not contain clay <br /> and where the soil modulus is at least 1000 psi. <br /> 131 RED THREAD II pipe is inherentlyflex ible.API Publication 1615 states. <br /> `Fiberglass piping,which is inherently flexible,does not require swing <br /> joints,if at least 4 feet of straight run is provided between any directional <br /> change exceeding 30-" <br />