Laserfiche WebLink
10. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Spec) <br />❑ Vacuum ® Hydrostatic <br />Test Equipment Used: Incon Sump Tester <br />Vapor Spill Box # 87 <br />Bucket Diameter: 12" <br />Equipment Resolution: +/-0.002" <br />Vapor Spill Box # 91 <br />12" <br />Bucket Depth: <br />10" <br />10" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min. <br />Test Start Time: <br />9:19 am <br />9:46 am <br />Initial Reading (RI): <br />4.6194 <br />7.2799 <br />Test End Time: <br />9:35 am <br />10:01 am <br />Final Reading (RF): <br />4.6191 <br />7.2795 <br />Test Duration: <br />16 min. <br />15 min. <br />Change in Reading (RF -RI): <br />0.0003 <br />0.0004 <br />Pass/Fail Threshold or <br />Criteria: <br />+/-0.002" <br />+/-0.002" <br />Test Result: <br />0 Pass ❑ Fail <br />© Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />FEB 0 3 2017 <br />ENVIRONMENTAL HEALTH <br />DEPARTMENT <br />