Laserfiche WebLink
9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer <br />❑ Other (Spec) <br />® Industry Standard ❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Spec) <br />❑ Vacuum N Hydrostatic —� <br />Test Equipment Used: Incon Sump Tester <br />Fill Spill Box # 87 <br />Bucket Diameter: 12" <br />Equipment Resolution: +/-0.002" <br />Fill Spill Box # 91 Fill Spill Box # Diesel <br />12" 12" <br />Bucket Depth: <br />10" <br />10" <br />10" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min. <br />10 min. <br />Test Start Time: <br />9:19 am <br />9:46 am <br />10:11 am <br />Initial Reading (Rj): <br />6.4398 <br />6.9125 <br />5.8172 <br />Test End Time: <br />9:35 am <br />10:01 am <br />10:26 am <br />Final Reading (RF): <br />6.4411 <br />6.9140 <br />5.8175 <br />Test Duration: <br />16 min. <br />15 min. <br />15 min. <br />Change in Reading (RF -RI): <br />0.0013 <br />0.0015 <br />0.0003 <br />Pass/Fail Threshold or <br />Criteria: <br />+/_0.002" <br />+/_0.002" <br />+/_0.002" <br />Test Result: <br />0 Pass 0 Fail <br />CRE Pass 0 Fail O Pass 0 Fail <br />Comments —(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />FE <br />ENVIRONMENTAL HEALTH <br />DEPARTMENT <br />