Laserfiche WebLink
RErl.=IVED <br /> SWRCB,January 2002 SEPPIO-M f <br /> 4. TANK ANNULAR TESTING ENVIRONMFNTAI HFP=AlTH <br /> Test Method Developed By: X Tank Manufacturer Industry Standard ❑Professio MWEHT <br /> ❑Other(Spec6) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - '/"x-301-1g. <br /> Tank# 1 Tank#2&3 Tank# Tank# <br /> Is Tank Exempt From Testing?' No No <br /> Tank Capacity: 12K 12K Split 6/6 <br /> Tank Material: Glass/Steel Glass/Steel <br /> Tank Manufacturer: Modern Welding Modern Welding <br /> Product Stored: Regular 87 Supreme 91/Diesel <br /> Wait time between applying 30 Minutes 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:30 10:40 <br /> Initial Reading(RI): -10 Hg. -10 Hg. <br /> Test End Time: 11:30 11:40 <br /> Final Reading(RF): -10 Hg. -10 Hg. <br /> Test Duration: 1 Hour 1 Hour <br /> Change in Reading(RF-Ri): 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. No loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? r I I <br /> Comments— (include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)1 <br />