My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO 2010 - 2018
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
M
>
MAIN
>
1100
>
2300 - Underground Storage Tank Program
>
PR0506504
>
COMPLIANCE INFO 2010 - 2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/20/2023 11:22:26 AM
Creation date
5/13/2019 8:45:42 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2010 - 2018
RECORD_ID
PR0506504
PE
2361
FACILITY_ID
FA0007464
FACILITY_NAME
MAIN STREET ARCO AM PM*
STREET_NUMBER
1100
Direction
S
STREET_NAME
MAIN
STREET_TYPE
ST
City
MANTECA
Zip
95337
APN
22119062
CURRENT_STATUS
01
SITE_LOCATION
1100 S MAIN ST
P_LOCATION
04
P_DISTRICT
005
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
296
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SAN J O A Q U I N 1 f� Environmental Health Department <br /> COUNTY 313I1$ ._w .^ <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MAIN STREET ARCO AM PM' 1100 S MAIN ST.. MANTECA March 12, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS it.or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 318 CCR 2636(f)(2) Leak detector failed to detect a 3.0 gph leak at 10 psi. <br /> The 87-octane, and 89-octane VMI line leak detector failed to detect a leak when tested. All line leak detectors shall <br /> be capable of detecting a 3-gallon per hour leak at 10 psi. The service technician adjusted the leak detector, <br /> retested it, and it passed. <br /> This was corrected on site. <br /> This is a minor violation. <br /> 320 CCR 2635(b)(2)Overfill prevention system not present or failed to meet overfill requirements. <br /> The red light bulb used for audio/visual alarm of the overfill prevention system was out.The light bulb was replaced <br /> and retested during the inspection.All underground storage tanks shall be equipped with an overfill prevention <br /> system that does not allow for manual override and meets one of the following requirements: <br /> 1. Alert the transfer operator when the tank is 90 percent full by restricting the flow into the tank or triggering an <br /> audible and visual alarm; or <br /> 2. Restrict delivery of flow to the tank at least 30 minutes before the tank overfills, provided the restriction occurs <br /> when the tank is filled to no more than 95 percent of capacity; and activate an audible alarm at least five minutes <br /> before the tank overfills; or <br /> 3. Provide positive shut-off of flow to the tank when the tank is filled to no more than 95 percent of capacity; or, <br /> 4. Provide positive shut-off of flow to the tank so that none of the fittings located on the top of the tank are <br /> exposed to product due to overfilling. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection. The EHD has written the <br /> complete report which replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork,within 30 days of receiving the complete inspection report. <br /> AFTER THE COMPLIANCE DATE,EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: Inspector: Inspector Phone: <br /> Printed Name and Title: AARON HANG, REHS (209)468-3453 <br /> FA0007464 PR0506504 SCO01 03/12/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />
The URL can be used to link to this page
Your browser does not support the video tag.