4\N J 1 ZOib <br />6. SECONDARY PIPE TESTING <br />Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ PmEec�h <br />IJC�ITV t�CD�DTp ICS <br />❑ Other fSpecift•1 <br />Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other 6Spe, il" <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0.5% of span <br />Piping Run # <br />91 Vent <br />Piping Run # <br />Diesel Vent <br />Piping Run # <br />Vapor <br />Piping Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Piping Manufacturer: <br />Ameron <br />Ameron <br />Ameron <br />Piping Diameter: <br />3" <br />3" <br />3" <br />Length of Piping Run: <br />80' <br />80' <br />100' <br />Product Stored: <br />N/A <br />N!A <br />N'A <br />Method and location of <br />piping -run isolation: <br />Reducer Rnnts/FitlinCs <br />RrJnry Roots/Fittings <br />Rcdnrer Rnnlx/Fittinax <br />Wait time between applying <br />pressure!vacuum/water and <br />starting test: <br />10 minutes <br />10 minutes <br />10 minutes <br />Test Start Time: <br />1030 am <br />10:30 am <br />10:30 am <br />Initial Reading (Ri): <br />5 psi <br />5 psi <br />5 psi <br />Test End Time: <br />11:30 am <br />11:30 am <br />11:30 am <br />Final Reading (RF): <br />5 psi <br />5 psi <br />5 psi <br />Test Duration: <br />I hr. <br />I hr. <br />I hr. <br />Change in Reading (RF-Ri): <br />None <br />None <br />None <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable Loss <br />No detectable Loss <br />No detectable Loss <br />Test Result: <br />1XI Pass ❑ Fail <br />IN Pass ❑ Fail <br />17 Pass ❑ Fail <br />Comments —(include informasian on repairs made prior /o /esring. and recommended foll(iw-up for failed tests) <br />