EL;lVtL, <br />UNDER -DISPENSER CONTAINMENT (UDC) TESTING JAN 11 2016 <br />Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Enine�Ier r�,T <br />❑ Other(.Speo/.i) ENVIRONMENTAL! <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />Cl Other (Spec• l.v) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +1- 0.002" <br />UDC At 9/10 <br />UDC # 11/12 <br />UDC # 13/14 <br />UDC # 15/16 <br />UDC Manufacturer: <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />UDC Material: <br />Fiberglass <br />Fiberglass <br />Fiberglas; <br />Fiberglass <br />UDC Depth: <br />31" <br />31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />of Hi hest Pipingg Penetration: <br />6" <br />6• <br />6'" <br />7" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />4.. <br />4" <br />4" <br />4" <br />Condition of UDC prior to <br />testing: <br />Good <br />Good <br />Good <br />Good <br />Portion of UDC Tested <br />2" above piping <br />2" above piping" <br />2" above piping <br />2" above piping <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />roducl and water)? <br />❑ Yes ❑ No ®NA <br />[]Yes ❑ No <br />NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />safe shutdown? <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® <br />NA <br />❑ Yes [I No ® NA <br />❑ Yes ❑ No U NA <br />Was fail-safe verified to be <br />operational?* <br />❑ Yes ❑ No ® NA <br />E] Yes ❑ No <br />NA <br />❑Yes ❑ No NA <br />❑Yes ❑ No NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting lest <br />30 minutes <br />30 minutes <br />30 minutes <br />30 minutes <br />Test Start Time: <br />1:32 pin <br />12:50 pin <br />12:50 pin <br />12:50 pin <br />Initial Reading (Ri): <br />5.5352 <br />15545 <br />2.7153 <br />1.2150 <br />Test End Time: <br />1:47 pin <br />1:06 pet <br />1:06 pro <br />1:06 pin <br />Final Reading(Ri:): <br />5.5355 <br />1.5545 <br />2.7153 <br />1.2149 <br />Test Duration: <br />15 min. <br />16 min. <br />16 min. <br />16 min. <br />Change in Reading (RF-Ri): <br />0.0003 <br />None <br />None <br />0.0001 <br />Pass/Fail Threshold or Criteria: <br />+1.0.00211 <br />+1-0.00211 <br />+1-0.002" <br />+/- 0.002" <br />Test Result: <br />El Pass ❑ Fail <br />® Pass D Fail <br />O Pass ❑ Fail <br />O Pass ❑ Fail <br />Was sensor removed for testing^ <br />®Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />E Yes ❑ No ❑ NA <br />Comments — (include mlormarion an repairs made prior la 1eaing, and )-ecnnintended follow-up,li,r )idled rests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />If the entire depth of the UDC is not tested. specify how much was tested. If the answer to agM of the questions indicated with an <br />asterisk(*) is "NO -or -NA". the entire UDC must be tested. (See SWRCB LG -160) <br />