Western Fiberglass Inc. <br />tern 1555 Copperhill Parkway <br />rglass Santa Rosa, Calif. 95403 <br />707/523-2050 <br />707/523-2046 fx <br />RECEIVEL <br />MAR 0 2 2015 <br />ENVIRONMENTAL. <br />Safeway Stockton — Site 2707 <br />On 2/27/15, technicians from Western Fiberglass were dispatched to repair <br />entry fittings in the vapor vent box for site 2707. <br />Upon arrival, technicians removed the lid to investigate the sump. The lid <br />had 4 bolts missing from the lid. One of the nuts for bolting down this lid <br />had been cut out and was missing. The other 3 missing bolts had nuts with <br />stripped threads, <br />The 4 entry fittings in the sump were in decay. The nuts holding on the <br />fittings, were removed and the studded fittings removed from the studsand <br />sump wall. The area behind the studded fittings was abraded and cleaned <br />with acetone. The threads on the bolts were cleaned and chased with a die to <br />insure the bolts were in good condition. <br />The splits on the studded split boots were bonded and left to cure. Upon <br />curing, the boots were bonded onto the sump wall around the studs. The nuts <br />were tightened and the bonder was. left to begin curing. <br />After the boot bonder had hardened, the 3 inch boots were filled with boot <br />filler. <br />All 3 of the test boots in this sump were replaced as an added measure. <br />As the bonders were curing, a retro fit kit for the lid was installed on the <br />sump. <br />Rick Misquez <br />Technician <br />