Laserfiche WebLink
Tracy Toyota Waste Anti -Freeze Tank Assessment <br />Written Assessment per CCR Title 22 , 66265.192, 66265.193 <br />Tracy Toyota Waste Antifreeze Seismic Calculation <br />Cylindrical, Vertical, Closed Top, Flat Bottom on Concrete Foudation <br />Material of Construction: LPE <br />Shell Height, in <br />Shell Diameter, in <br />Volume of Tank, in3 <br />Volume of Tank, gallons <br />Working Volume, gal <br />S.G. of contents <br />Weight of Contents, lbs <br />Tank Wall Thickness, in <br />Wt of Tank, lbs <br />Total Weight of Tank and Contents, lbs <br />Zip Code <br />Overturning Moment Arm, in <br />Resisting Moment Arm, in <br />Soil Class D <br />Sds <br />Importance Factor <br />Fp, ASCE 7-05,15.4-5 <br />Resisting Moment, inlbf <br />Overturning Moment, inlbf <br />Factor of Safety for Overturning <br />Shear Strength of Anchor. Lbs <br /># of Anchors <br />Factor of Safety for Shear <br />Figure 5, Waste Antifreeze Tank Seismic Calculation <br />Seismic/Anchoring findings: The tank as esig <br />containment area in which it is located are ad u� <br />seismically sound. Initials: _ <br />and <br />anc <br />49.00 <br />36.00 <br />49850.64 <br />215.80 <br />194.22 <br />1.05 <br />1700.81 <br />0.33 <br />85.70 <br />1786.51 <br />95304 <br />22.05 <br />18.00 <br />0.96 <br />1.00 <br />515.59 <br />32157.24 <br />11368.71 <br />2.83 <br />1480.00 <br />1.00 <br />2.87 <br />ted and the <br />and are <br />Strandberg Associates 1(866) 388-0404 (650) 329-3918 rwaterguvcc'7.rwaterguy.com 6 <br />