Laserfiche WebLink
Owens-Brockway Spill Prevention,Control,and Countermeasure Plan <br /> Plant#22 <br /> Table 2.1 <br /> Secondary Containment Volume Calculations <br /> Plant#22 <br /> Tracy,California <br /> Secondary Containment Area (1)180 gal Diesel Tank NOAA 25-YR 24-HR[NOAH Atlas 14 Volume 8 Version 2 Precipitation-Frequency Atlas of the United States(2013)] <br /> (Tank A) <br /> Containment Type(Large Tanks) Concrete Rainfall(in) 2.28 <br /> Berm Length(ft) 6.7 Area(f 2) 25 <br /> Berm Width(ft) 3.8 Rainfall Displacement Volume(gals) 36 <br /> Containment Height(ft) 2.0 <br /> Containment Volume(gals) <br /> Largest Tank-(1)300 gal Diesel Tank <br /> Diameter(ft) NA <br /> Radius(ft) NA <br /> Height(ft) NA <br /> Quantity 1 <br /> Largest Tank Shell Volume(gals) <br /> Calculation Summary <br /> Containment Volume(gals) 378 <br /> Largest Tank Shell Volume(gals) 300 <br /> Total Displaced Volume(gals) 0 <br /> Rainfall Dis lacement(gals) 36 <br /> Excess/Deficiency for 100%release plus a Rainfall Event(gals) 42 <br /> Excess/Deficient for 110%release(gals) 48 <br /> cHDi 890s1uOiAPPs GHD Services,Inc. <br />