Laserfiche WebLink
_ r <br /> .,s <br /> m- <br /> integrity Tank Testing STP-4-ems,Inc. <br /> RECEIVED DEC 2 8 X90 <br /> December 24, 1990 <br /> Mr. Lois France <br /> Waterwork Corporation <br /> 1710 Main Street <br /> Escalon, California 9320 <br /> Site: RrEVE'S EXXON STATION, Tracy, CA <br /> ig <br /> Dear Mss France: <br /> Following is a summ <br /> of the precision testing we recently <br /> ary <br /> conducted on your underground storage tank(s) . <br /> i, graphs, and <br /> Enclosed are copies of the test worksheets l P <br /> computer generated data for your submittal to the <br /> appropriate governmental agency. <br /> y <br /> A tank system may be considered tight:, according to the <br /> current regulations if the thetestresults shown below do <br /> - <br /> � --' not exceed 0.05 gph. if the re ayhavereocbeyond <br /> urred, and <br /> unauthorized release m <br /> parameter, anay <br /> t you should consider taking remedial action. <br /> f ; <br /> PRODUCT TEST WITHIN TIGHT <br /> TAFK # OR TANK CONTAINED RESULTS <br /> PARAMETERS <br /> E, LOCATION CAPACITY <br /> - <br /> North 5,500 Diesel -.029 <br /> Yes <br /> U/L, Gas -.011 Yes <br /> Center 5.500 - .139 No** <br /> South 5.500 Sup U/L <br /> **SEE PAGE 2. <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> W. .N. Savage <br /> Certified Tester <br /> 600 267•$378 <br /> 166 Freak West Circle <br /> Stx]rtDn.CA 95206 909)4664W6 <br />