Laserfiche WebLink
SWRCB, January 2002 <br />7. UNDER -DISPENSER CONTAINMENT DQ TESTING <br />Page _ of <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard ❑ Professional Engineer II <br />n+U-, 2�„�..��1 rairlwPil Cmmn Tester <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Sump Tester Equipment Resolution: 0.005 inches in <br />UDC # 1 UDC # 2 UDC # 3 UDC # <br />UDC Manufacturer: <br />Unknown <br />Unknown <br />Unknown <br />UDC Material: <br />Plastic <br />Plastic <br />Plastic <br />UDC De the <br />14 inches <br />14 inches <br />14 inches <br />Height from UDC Bottom to Top <br />0 inches <br />0 inches <br />0 inches <br />of Hi est Pi in Penetration: <br />Height from UDC Bottom to <br />4 <br />4 <br />4 <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />Dry <br />Dry <br />Dry <br />E4r_ Ir-rU nc0I07jocA1 <br />testing: <br />Portion of UDC Tested <br />8 inches <br />8 inches <br />8 inches <br />®Yes ❑ N o ❑ NA <br />Eyes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?` <br />3 sec <br />N yes ❑ No ❑ NA <br />3 sec <br />® Yes ❑ No ❑ NA <br />3 sec <br />® Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Turbine shutdown response time <br />Is system programmed for fail- <br />safe shutdown? <br />®yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />® Yes 11 No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was fail-safe verified to be <br />o erational?" <br />Wait time between applying <br />5 min <br />5 min. <br />5 min. <br />pressure/vacuum/water and <br />test <br />startin <br />Test Start Time: <br />1:30 <br />1:30 <br />2:15 <br />Initial Reading (Rs): <br />1st Rin <br />13'Rin <br />V Rin <br />2:00 <br />2:00 <br />2.45 <br />Test End Time: <br />Final Readin (RF): <br />tat Rin <br />1'' Rin <br />I't Ring <br />30 min. <br />30 min. <br />30 min. <br />Test Duration: <br />Chan a in Reading (RF-Rj): <br />0 chane <br />0 chan e <br />0 change <br />Pass/Fail Threshold or Criteria: <br />0.005 inches in 1/2 <br />0.005 inches in %: 0.005 inches in 1/2 <br />hour <br />hour hour <br />® Pass ❑ Fail <br />® Pass ❑ Fail ® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Result: <br />Test <br />®Yes, ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />N Yes ❑ No ❑ NA ®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor removed for testing? <br />Was sensor properly replaced and <br />verified functional after testing? <br />Comments (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to gpy of the questions indicated with an <br />asterisk (*) is "NO" or "NA', the entire UDC must be tested. (See SWRCB LG -160) <br />