Laserfiche WebLink
The combined volume of the tank and ancillary equipment: <br /> Item 0gantilty Len th inch ID inch Volume (gallon) <br /> Storage Tank 1 500 <br /> Piping Pump to Tank 1 210 1.049 0.79 <br /> Transfer Pump 1 0.4 <br /> Suction Wand 1 70 0.75 0.13 <br /> Total 501.2 <br /> The secondary containment capacity of 521 gallons will contain 100% of <br /> the tank capacity and ancillary equipment. This meets the requirement <br /> specified in 22CCR66265.1920)(1). <br /> Visual inspection of containment area: 66264.193(e)(2) <br /> The secondary containment tank is in good condition with no evidence of <br /> damage or corrosion. The space was completely empty. <br /> Secondary Containment findings: The secondary containment system is of <br /> sufficient capacity and condition for the containment of releases from all <br /> tanks and ancillary equipment. <br /> Initials: K <br /> Initial Discrepancies and Corrections Taken: <br /> Discrepancy: None <br /> Correction Taken: None <br /> Kia Country - Manteca 7 Title 22 Waste Oil Assessment <br />