Laserfiche WebLink
R I CH ZYUR ONMENTAL <br />5643 BROOKS CT BAKERSFIELD,CA.93308 <br />OFFICE(661)392-8687 & FAX (661)392-0621 <br />AES MODEL PLT-10OR HYDROSTATIC PRODUCT LINE TEST <br />Precision Product Line Test <br />TEST RESULTS <br />JOB#: <br />Test Date:02-16-2001 <br />BILLING:L.C. SERVICES <br />527 N.PARKVIEW <br />FRESNO, CA 93728 <br />SITE:SHELL <br />4315 WATERLOO RD <br />STOCKTON, CA. <br />PRODUCT PRODUCT MECHANICAL MONITOR <br />PRODUCTS LINE TEST LEAK DETECTOR LEAK DETECTOR <br />1)PREMIUM <br />-0.050-FAIL NO TEST ANNULAR & SUMP <br />2)PREMIUM <br />-0.026-PASS <br />3)PREMUIM <br />-0.013-PASS <br />4)PREMIUM <br />-0.005-PASS <br />5)PREMIUM <br />-0.006-PASS <br />6)PREMIUM <br />-0.002-PASS <br />7)PREMIUM <br />-0.002-PASS <br />8)PREMIUM <br />-0.001-PASS <br />9)PREMIUM <br />-0.001-PASS <br />10)PREMIUM <br />-0.000-PASS <br />COMMENTS <br />A precision test was performed on product lines at the above location <br />using the AES MODEL PLT-10OR HYDROSTATIC PRODUCT LINE TEST. I have <br />reviewed the data produced in conjunction with this test for purpose of <br />verifying the results and certifying the product line test -systems. <br />The testing was performed in acorrdance with AES protocol, and <br />therefore satisfies all requirements for such testing as set forth by <br />NFPA 329-92 and USEPA 40 CFR part 280. <br />The results of testing are shown on the following page. Included with <br />the report are reproduction of data compiled during the test which <br />formed the basis for these conclusion. This information is stored in a <br />permanent file if future verification of test results is needed. <br />AL\NC 040 <br />Test Certified By: <br />/A� <br />ames J. Rich <br />State cert#99-1072 <br />