CHRONOLOGY <br /> ARTS & ARTISTS <br /> 204 LODI AVENUE, LODI <br /> 12/31/86 550 gallon gasoline UST removed and soil from removal was <br /> placed back in the excavation. <br /> 1187 A City of Lodi municipal well located 350 feet east of the UST <br /> location was sampled and the results were ND. This well was later <br /> destroyed, sometime prior to June 1992. <br /> 7123-23187 Monitoring wells MW1, MW2, MW3 were installed. Respective <br /> screen intervals for these wells were 35'-65', 40'-60', 39'-59'. <br /> Groundwater level beneath surface was about 50'. MW1 is located <br /> about 15' east of the former UST location. MW3 is located about <br /> 40' southeast of the former UST location. MW2 is located about <br /> 75' southwest of the former UST location. MW1 & MW3 evidenced <br /> groundwater contamination. The gradient was northeast. <br /> 11191 MW2 &MW3 were dry. MW1 had floating product. <br /> 6129-30192 MW4 & MW5 were installed, with screen intervals of 49'-74' and <br /> 50'-75' below surface. The gradient was northeast. <br /> 10/23/92 MW1, MW4 & MW5 were sampled. Depth to groundwater was <br /> about 61' below surface. MW1 had high levels of groundwater <br /> contamination. MW4 & MW5 had low levels of groundwater <br /> contamination. <br /> 4112-13193 MW6, MW7 & MW8 were installed to define the groundwater <br /> plume. All wells were screened from 50'-70' below surface. The <br /> depth to groundwater was about 55' below surface. <br /> 4/27/93 MW1, MW4, MW5, MW6, MW7, MW8 were sampled. The gradient <br /> was southerniy. MW1 had high levels of groundwater <br /> contamination. MW4 & MW5 low levels of groundwater <br /> contamination. MW6, MW7, MW8 were ND. <br /> 8/18/93 RW1 was installed in a slant boring about 10' southeast of the <br /> former UST location, with screen intervals 10'-40' and 45'-50'. <br /> 12/17/93 A vapor extraction test was performed on RW1. <br />