The following is an itemized list of underground storage tank violations that have not <br /> been addressed for CRUISERS MANTECA#29 as of April 13, 2018. <br /> Open violations from August 25, 2016 inspection <br /> Violation#316 -Secondary containment not constructed to prevent water intrusion (after Jul 2003). <br /> Water was found in the 91 STP and Diesel STP sumps(both sides of the sump had liquid). Secondary containment <br /> shall be constructed to prevent any water intrusion into the system by precipitation, infiltration, or surface runoff. <br /> The service technician wasn't able to remove all the liquid from above sumps. Immediately contact a properly <br /> licensed, trained, and certified contractor to remove the observed liquid and to investigate and address the <br /> water/liquid intrusion into these sumps under permit and inspection of the EHD. <br /> Open violations from July 14, 2016 inspection <br /> Violation #314 -Failed to have secondary containment or secondary containment not tight. <br /> Liquid with some fuel odor(per the technician onsite)was found in the diesel STP sump, which had the newly <br /> installed Bravo Snap and Lock cover. L5 sensor(diesel STP sump brine sensor) was in alarm for low brine level at <br /> the time of inspection. The technician onsite added brine to the L5 sensor reservoir and "all functions normal"was <br /> observed at the panel. Also, yellow glue (similar to that used in the 87 fill sump) was observed around the sump <br /> penetration. The technician removed approximately 4-5 cups of liquid and placed it in the onsite hazardous waste <br /> container. Secondary containment shall be impervious to the liquid and vapor of the substance contained and <br /> constructed to prevent structural weakening as a result of contact with any hazardous substances released from the <br /> primary containment. Immediately contact a properly licensed, trained, and certified contractor to make repairs to <br /> the UST system under permit and inspection of the EHD, or immediately submit a permit for any un-permitted <br /> repairs already conducted on this sump. <br /> Open violations from August 19, 2015 inspection <br /> Violation #204 -Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> Page 4 of 4 <br />