Laserfiche WebLink
'SWRCB,January 2002 11,1(,e z <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: F-1 Tank Manufacturer ❑% Industry Standard F-1 Professional Engineer <br /> 11 Other (Spec) <br /> Test Method Used: ❑ Pressure ❑% Vacuum F] Hydrostatic <br /> 0 Other (Specify) <br /> i <br /> st Equipment Used: Equipment Resolution: <br /> Tank# 1 REG Tank# 2 SUP Tank# Tank# <br /> Is Tank Exempt From Testing?I Yes M No ❑Yes X No F-1 Yes D No 1:1 Yes ❑No <br /> Tank Capacity: 20,000 10,000 <br /> Tank Material: FRP CLD ST FRP CLD ST <br /> Tank Manufacturer: unknown unknown <br /> Product Stored: REGULAR SUPREME <br /> Wait time between applying <br /> pressure/vacuum/water and 5min 5min <br /> starting test: <br /> Test Start Time: 9:43 9:41 <br /> Initial Reading(RI ): 7hg 7hg <br /> Test End Time: 10:43 10 :41 <br /> Final Reading(RF ): 7hg 7hg <br /> Test Duration: 1hr 1hr <br /> Change in Reading(RF-P4 ): 0 0 <br /> Pass/Fail Threshold or Criteria: 1 .7hg 1.7hg <br /> Test Result: Pass 1:1 Fail �Pass D Fail 1:1 Pass El Fail E]Pass D Fail <br /> Was sensor removed for testing? X Yes[:]N NAx❑Yes❑NcCINA❑Yes[:]N NA 0YesF]NeCNA <br /> Was sensor properly replaced and ❑ � � � � ❑ � � ❑ <br /> verified functional after testing? X Ye_ N NA X Ye N NA Ye N NA Ye N( NA <br /> Comments- (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />