Laserfiche WebLink
• "No Smoking" and "Keep Fire Away" signs (or equivalent) are posted and no <br />smoking or open flames are allowed within 25 feet of a tank holding less than <br />1,200 gallons, and 50 feet of a tank holding more than 1,200 gallons of a <br />flammable or combustible material or waste. <br />3. Welding and Cutting Operations <br />• A fire extinguisher or hose is available where a torch is used inside buildings. <br />• A fire watch is conducted for one 1/2 -hour after a torch is used, or after <br />cutting or welding is performed. <br />• No welding or cutting is performed on tanks, drums, or other containers that <br />have contained flammable liquids unless they have been thoroughly purged <br />and tested inside with a combustible gas detector. <br />• The area surrounding the cutting or welding operation is free of all flammable <br />or combustible materials, liquids, or vapors, lint, and dust. <br />• Cylinders, piping, valves, regulators, and hoses are prevented from coming in <br />contact with oil and oily substances. <br />• Cylinders in use are placed far enough away from welding to avoid heat by <br />radiation from heated materials, sparks, or slag. <br />• All cylinders in use have a pressure -regulating dev;ce. <br />• Hoses are regularly inspected for leaks, burns, tears, loose connections, and <br />other defects. Where two hoses are joined by a web, they are of different <br />colors or textures. <br />4. Painting Operations <br />"NO SMOKING" and "NO WELDING" signs are posted, and painting <br />operations are separated by at least 20 feet or a fire wall from any source of <br />flame or sparks. Only non -sparking tools are used. <br />• Contamination by any foreign substance is prevented, and spilled materials are <br />immediately cleaned up with noncombustible solvent and absorbent and <br />disposed of outside the painting area in closed containers. <br />• Discarded spray gun filter pads are immediately disposed of in a closed <br />container outside the work area location, or else placed in a water -filled <br />container and removed daily at the close of operations. <br />• Only non-combustible spray filters are used. <br />4-3 <br />