Wildwood LNG Demonstration Facility <br /> 5.6 Water-Glycol Cooling Loop System <br /> The purpose of the water-glycol cooling loop system is to remove heat from the refrigeration <br /> system. The system consists of four heat exchangers, one pump, and a surge tank. The cooling <br /> liquid is a mixture of 90% water and 10% glycol. Table 7 presents the design information used <br /> for the cooling loop system. <br /> The circulation pump recovers cooling fluid in the surge tank. The pump circulates <br /> approximately 80 gpm through an air cooler. The air cooler rejects approximately 2,000,000 <br /> Btuihour to the atmosphere. The cooling water is then split between several heat exchangers that <br /> cool the compressor oil, the expander oil, and refrigeration nitrogen after compression. The <br /> cooling water than returns to the surge tank. Make-up water and glycol will be added to the <br /> surge tank as required. Water and glycol will not be stored on the site, but will be delivered by <br /> truck as needed. The surge tank includes one emergency safety relief valve that will vent to the <br /> atmosphere if overpressure is encountered in the tank. <br /> Table 7 <br /> Design Information for the Cooling Loop System <br /> Equipment Equipment Name Pressure—(PSIG) Temperature (°F) Flow Rate <br /> Number Operating/Design Operating/Design <br /> 90-1901 Circulation Pump 55/100 85/125 110 gpm <br /> 90-3201 Air Cooler 55/100 85/125 110 gpm <br /> 30-3207 Expander Oil 55/100 85/125 110 gpm <br /> Cooler <br /> 30-3211 Compressor Oil 55/100 85/125 110 gpm <br /> Cooler <br /> 30-3209 Refrigeration 55/100 85/125 110 gpm <br /> Nitrogen Cooler <br /> 5.7 Product Storage Tank <br /> The proposed project will utilize a cryogenic tank for storage of the LNG product. It will be <br /> manufactured by Process Engineering of Plaistow, New Hampshire in accordance with NFPA <br /> 59A, Chapter 10. The nominal capacity of the tank is 15,000 gallons. Its approximate <br /> dimensions are 10 feet in diameter by 37 feet long. The tank will be fitted with appropriate <br /> control valves and instrumentation as indicated in Figures 7 and 8. <br /> AES Construction Group <br /> Page 10 <br />