4. TANK ANNULAR TESTING _ <br /> Test Method Developed By: ❑Tank Manufacturer ®lndustry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ®Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Test plugs,venturi pump and gauges Equipment Resolution: 0.5% of span <br /> Tank#Diesel <br /> Is Tank Exempt From Testing?) ❑ Yes ® no <br /> Tank Capacity: 6,000 <br /> Tank Material: Steel <br /> Tank Manufacturer: Xerxes <br /> Product Stored: Diesel/Water <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min. <br /> starting test: <br /> Test Start Time: 11:15 am <br /> Initial Reading(Rj): T'hg <br /> Test End Time: 12:1.5 pm <br /> Final Reading(RF): T'hg <br /> Test Duration: l hour <br /> Change in Reading(RF-R,): None <br /> Pass/Fail Threshold or Criteria: No Detectable Loss <br /> Test Result: ®Pass Fail <br /> Was sensor removed for testing? ❑Yes®No ❑NA <br /> Was sensor properly replaced and ❑ Yes❑No ®NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />