6. PIPING SUMP TESTING _ <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Spec) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> STP Sump#Diesel <br /> Sump Diameter: 42" <br /> Sump Depth: 59" <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of 14" <br /> -Highest Piping Penetration: <br /> Height from Tank Top to Lowest 28" <br /> Electrical.Penetration: _ <br /> Condition of sump prior to testing: Good <br /> Portion of Sump Tested' 2"above piping <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑ Yes❑ No ©NA <br /> -product and water)?* <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail-safe <br /> shutdown?` ❑ Yes❑No ®NA <br /> Was fail-safe verified to be <br /> o erational?* ❑Yes❑No ®NA <br /> Wait time between applying <br /> pressure/vacuumiwater and starting 30 minutes <br /> test: <br /> Test Start Time: 12:21 pm <br /> Initial Reading(Rt): 3.6553 <br /> Test End Time: 12:36 pm <br /> Final Reading(RF): 3.6571 <br /> Test Duration: 15 min. <br /> Change in Reading(RF-Rt): +0.0018 <br /> Pass/Fail Threshold or Criteria: +/-0.002" <br /> Test Result: © Pass 0 Fail <br /> Was sensor removed for testing`. ®Yes❑No ❑NA <br /> Was sensor properly replaced and ®Yes❑No ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />