KLEIN FELDER <br /> N File No. 23480020.D00 <br /> August 26, 1994 <br /> rl <br /> • That environmental soil and/or groundwater remediation will occur after the tanks have been <br /> removed and the excavation backfilled. <br /> We recommend that drilled cast4n7place piers be used to underpin the garage foundation. The <br /> existing foundation should be connected to the drilled pier in a manner such that the column loads <br /> of the building are transferred to the drilled piers. Piers should be placed under every column load <br /> and every 10 feet on center whichever is less. Piers should embed at least five (5) feet past the <br /> depth of excavation. The recommended friction value for drilled piers is 1 ,200 psf for the clayey <br /> and sandy silt soil anticipated below the depth of tanks. Since the upper portion of drilled pier <br /> will likely be exposed by the excavation; minimal lateral support of the piers is expected. <br /> ;j Probably the most effective means of providing lateral support for the existing footings may be <br /> within the building itself, such as a structural connection to the floor slab. We recommend that <br /> the actual design of the drilled piers and evaluation of lateral support be provided by a structural <br /> engineer. <br /> A copy of this report should be submitted to the San Joaquin County Environmental Health <br /> Department. This report and the conclusions and recommendations presented are subject to the <br /> "Limitations" presented in Chapter 7.0 of this report. <br /> a <br /> i <br /> i <br /> � I <br /> EIrl:md 7EI94 <br /> Copyright 1994 Kleinfelder, Inc. Page 12 of 14 <br />