Laserfiche WebLink
SHAWN Environmental Health Department <br /> COU NTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 99 SHELL* 1 7700 MORELAND ST STOCKTON August 29 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 121 CCR 2712(f Failed to submit a written response within 30 days of receiving an inspection report. <br /> An inspection was last done on 9/6/2018 and an inspection report was issued identifying information to be submitted <br /> to bring this site into compliance. This information was required to be submitted by 10/6/2018. This information has <br /> not been received resulting in a non-compliant status for this facility. An operator that receives an inspection report <br /> shall have 30 days to implement the corrections specified in the inspection report and comply with permit conditions. <br /> The corrective action shall include all of the recommendations made in the report.The operator shall submit a written <br /> response that includes a statement documenting corrective actions taken or proposing corrective actions which will be <br /> taken. Ensure that a written response documenting corrective actions taken or proposed is submitted and all <br /> corrections implemented within 30 days of receiving an inspection report. <br /> This is a Class II violation. <br /> 204 CCR 2712(1)Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be accessible <br /> on site at all times. Immediately locate and retain a copy on site. <br /> This is a Class II violation. <br /> 205 CCR 2712(i), 2634(e)Failure to submit a current UST Response Plan and have it available onsite. <br /> An approved copy of the response plan was not available for inspection. A copy of this plan shall be accessible on <br /> site at all times. Immediately locate and retain a copy on site. <br /> This is a Class II violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> 1)A designated operator inspection was performed on February 18, 2019 and the next inspection was performed on <br /> March 21,2019, 31 days later. The designated operator visual inspections shall be conducted within 30 days or less <br /> of the previous inspection. Ensure that all designated operator inspections are performed within the required time <br /> frames. <br /> 2)The designated operator failed to check and note all required items on the visual inspection reports. <br /> -Section V of the inspection reports were missing follow up actions about scheduling Overfill Prevention Equipment <br /> Testing. <br /> -Section VI of the report was missing the date, name, and signature of the UST owner/operator. <br /> -The designated operator documented visual inspections of UDCs, but left the question regarding UDC sensor <br /> locations blank. <br /> During the visual inspection,the designated operator shall check that all required testing and maintenance for the UST <br /> system have been completed and shall check all required items on the report. Ensure that designated operators <br /> performing visual inspections at this facility are including all of the required information on the reports. <br /> This is a Class II violation. <br /> FA0003732 PR0231819 SCO01 08/29/2019 <br /> EHD 23-01 Rev.08/27/2019 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />