Laserfiche WebLink
AK Tf_ <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> Date: APR 9, 2008 Work Order# 08040901-5 <br /> Location: MANTECA EXPRESS Contact: BOBBYMANGAT <br /> 419 S. MAIN STREET <br /> MANTECA, CA 95336 Telephone: (209)401-5292 <br /> SUMP# 1 2 3 <br /> PRODUCT 91 87 DIESEL <br /> LD TYPE Mechanical, W PLLD, (P)LLD I M M M <br /> LD MANUFACTURER VAPORLESS REDJACKET REDJACKET <br /> LD MODEL LD 2000 FXIV FXIV <br /> LD SERIAL NUMBER 05011178 1181 2631 <br /> SUMP CONDITION DRY DRY DRY <br /> RESILIENCY 32 ML 35 ML 20 ML <br /> OPERATING PRESSURE 28 PSI 28 PSI 28 PSI <br /> OPENING TIME 3 SEC 3 SEC <br /> METERING PRESSURE 10 PSI 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 12 PSI 12 PSI 12 PSI <br /> LEAK RATE LD DETECTED OVER 3 GPH 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? NO YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? NO NO NO <br /> LD PASS OR FAIL? FAIL PASS PASS <br /> Comments: <br /> 91 LEAK DETECTOR TO BE REPLACED&RETESTED ON APRIL 10, 2008 <br /> Technician: Mike Lawrence Contractor Lic. # 803705 <br /> Signature: <br /> TANK-TEK ENVIRONMENTAL CORPORATION <br /> 607 Elmira Road,PMB 336,Vacaville,CA 95687 — Ph.(707)446-6151 - Fax (707)446-6192 - E-mail:tank-tek@cwnet.com <br /> 31828 Cercle Chambertin,Temecula, CA 92591 — Ph. (951)699-8058 - Fax(951)699-8059 - E-mail:drbtanktek@sdccu.net <br />