Laserfiche WebLink
2.1.3.5.Do not roll the tank to move it. 3.1.6.When checking the tank for leaks during an air/soap test, <br /> rotate the tank to check the bottom,unless it is a tank filled with <br /> 2.1.3.6.When handling a tank with a bottom sump or fitting,always monitoring fluid. <br /> take extra care so that the bottom sump or fitting is not damaged by <br /> contact with any other object,such as the truck bed or the ground. CAUTION <br /> Never rotate a tank filled with monitoring fluid.See <br /> 2.1.4.Whenever a tank is temporarily placed aboveground at SECTION 3.4.and SECTION 3.8.for instructions regarding <br /> the site,chock it in place to prevent rolling. (See FIGURE 2-3.) these tanks. <br /> Tie the tank down if high winds are expected. <br /> 3.1.7.Before rotating the tank during an air/soap test,place <br /> protective material on the area on which the tank will be rotated. <br /> Tie <br /> Downs Make sure the area is flat and is free of large or sharp objects, <br /> such as rocks,which may damage the tank. <br /> Sandbags Tres <br /> Tank 3.1.8.Rotate the tank slowly and carefully to avoid developing <br /> too much momentum.Momentum can grow because fittings on <br /> top of the tank make it top heavy. Make sure the tank's fittings <br /> and manways never touch the ground.Do not rotate the tank <br /> more than 120°from the initial starting point. <br /> FIGURE 2-3 1A WARNING <br /> 3. PREINSTALLATION TESTING Always secure the tank before moving or lifting it.This is <br /> commonly done by connecting a crane or backhoe to the <br /> 3.1.GENERAL lifting lugs.Failure to do so could result in death or serious <br /> 3.1.1.Xerxes tanks are tested prior to shipment,but the tank injury. <br /> must be retested at the site prior to installation—even if shipped <br /> with the optional vacuum in the interstitial space or wet A WARNING <br /> interstitial space—in order to verify the absence of shipping and While moving or lifting the tank,do not position any part of <br /> handling damage. your body underneath the tank. This could result in death <br /> 3.1.2.The tester is responsible for verifying that all of the test or serious injury. <br /> equipment is in good working condition,and is properly <br /> configured and calibrated. A WARNING <br /> 3.1.3.Construct a test manifold with two air-supply gauges as Do not lift or hoist a tank under pressure. This could resultin death or serious injury. <br /> shown in FIGURE 3-1.Each air-supply gauge must have a <br /> maximum full-scale reading of 15 psig with 1/4-Ib.or 1/10-Ib. 3.1.9.Refer to the appropriate section below for instructions for <br /> increments,and a pressure-relief device set at 6 psig[4 psig for the following situations: <br /> 12-foot-diameter tanks]. <br /> 3.1.9.1.For testing a single-wall tank,see SECTION 3.2. <br /> Gauge <br /> JK—_Ai,-Supply <br /> Valvely g dry 3.1.9.2.For testing a double-wall tank with a d interstitial <br /> Air-Supp <br /> Gauge space,see SECTION 3.3. <br /> Pressure-Relief 3.1.9.3.For testing a double-wall tank with a wet interstitial <br /> Device space,see SECTION 3.4. <br /> FIGURE 3-1 3.1.9.4.For testing a single-wall multicompartment tank with a <br /> 3.1.4. In air tests,temperature change could be a factor in single-wall bulkhead,see SECTION 3.5. <br /> changes in gauge readings. 3.1.9.5.For testing a single-wall multicompartment tank with <br /> Note: Multiple test manifolds are required to test double-wall bulkhead(s),see SECTION 3.6. <br /> multicompartment tanks. 3.1.9.6.For testing a double-wall multicompartment tank with a <br /> 3.1.5. It is the installer's responsibility to select a thread sealant dry interstitial space,see SECTION 3.7. <br /> that is compatible with the product being stored.Some sealants 3.1.9.7.For testing a double-wall multicompartment tank with a <br /> cannot be used with some products.Remove,clean and redope wet interstitial space,see SECTION 3.8. <br /> all factory-furnished temporary plugs with appropriate thread <br /> sealant. Install permanent plugs in all openings where piping will 3.1.10. If damage is detected,do not attempt repairs.Contact <br /> not be installed.Make sure all manway bolts are tightened,and the UST coordinator at the Xerxes plant nearest you.Telephone <br /> fitting plugs are properly doped and sealed. and fax numbers are found on the back cover of this manual. <br /> 4 <br />