Laserfiche WebLink
3.5.TESTING A SINGLE-WALL MULTICOMPARTMENT TANK 3.5.3.AIR TEST OF END TANK(S) <br /> WITH A SINGLE-WALL BULKHEAD 3.5.3.1.Connect the pressure source to the test manifold on the <br /> 3.5.1.GENERAL end tank(s).(See FIGURE 3-3 and FIGURE 3-8.) <br /> 3.5.1.1.Remove all temporary service-fitting plugs. <br /> 3.5.3.2.Pressurize the end tank(s)to 5 psig[3 psig for a <br /> 3.5.1.2.Redope fittings and install plugs in all openings,except 12-foot-diameter tank].Allow the pressure to stabilize by adding <br /> one service fitting in each compartment(needed for the test or removing air as necessary. <br /> manifolds).Follow instructions in Point 3.1.5. (See FIGURE 3-6 <br /> and FIGURE 3-7.) 3.5.3.3.Close the air-supply valve on the test manifold. <br /> Disconnect the air-supply line. <br /> 3.5.1.3.Before doing the air test of the base tank(described in <br /> SECTION 3.5.2.)and the air test of the end tank(s)(described in 3.5.4.EXTERNAL SOAP TEST <br /> SECTION 3.5.3.),install the test manifolds on the base and end 3.5.4.1.Soap the entire exterior of the tank,checking for leaks. <br /> tank(s). (Follow instructions in Points 3.1.6.through 3.1.8.,including <br /> Warnings following 3.1.8.)Watch for active air bubbles,which <br /> indicate a leak.Pay special attention to fittings and manways. <br /> Lifting Lug_. Typical Service Fitting Monitor Fitting <br /> Typical Manway with Fillings' When Double-Wall 3.5.4.2.Monitor the pressure for one hour. <br /> i Bulkhead Is Used <br /> 3.5.4.3.After the test is completed,release all tank air pressure <br /> ( End Tank Base Tank End Tank and remove gauges. <br /> 3.5.4.4.Replace the protective covers in the service fittings. <br /> Bulkhead \ Flat <br /> Seam for nib 3.6.TESTING A SINGLE-WALL MULTICOMPARTMENT TANK <br /> Seam for Base Tank Seam for <br /> End Tank End Tank WITH DOUBLE-WALL BULKHEAD(S) <br /> FIGURE 3-6 <br /> CAUTION <br /> Air Test of Base Tank Do not connect air supply directly to the interstitial-space <br /> monitor fitting.Pressurizing the secondary tank(interstitial <br /> e s e e e space)by itself may damage the primary tank or cause tank <br /> failure. <br /> 3.6.1.GENERAL <br /> 3.6.1.1.Remove all temporary service-fitting plugs. <br /> 3.6.1.2.Redope fittings and install plugs in all openings,except <br /> FIGURE 3-7 one service fitting in each compartment(needed for the test <br /> manifolds).Follow instructions in Point 3.1.5. (See FIGURE 3-6 <br /> Air Test of End Tank(s) and FIGURE 3-7.) <br /> s e e o 3.6.1.3.Before doing the air test of the base tank(described in <br /> ' SECTION 3.6.2.)and the air test of the end tank(s)(described in <br /> SECTION 3.6.3.),install the test manifolds on the base and end <br /> tank(s). <br /> 3.6.2.AIR TEST OF BASE TANK <br /> FIGURE 3-8 3.6.2.1.Connect the pressure source to the test manifold on the <br /> base tank.(See FIGURE 3-3 and FIGURE 3-7.) <br /> 3.5.2.AIR TEST OF BASE TANK 3.6.2.2.Pressurize the base tank to 5 psig[3 psig for a 12-foot- <br /> 3.5.2.1.Connect the pressure source to the test manifold on the diameter tank].Allow the pressure to stabilize by adding or <br /> base tank.(See FIGURE 3-3 and FIGURE 3-7.) <br /> removing air as necessary. <br /> 3.5.2.2.Pressurize the base tank to 5 psig[3 psig for a 12-foot- 3.6.2.3.Close the air-supply valve on the test manifold on the <br /> diameter tank].Allow the pressure to stabilize by adding or base tank.Disconnect the air-supply line. <br /> removing air as necessary. <br /> 3.5.2.3.Close the air-supply valve on the test manifold in each 3.6.2.4.Soap the fittings on top of the base tank to make sure fittings <br /> compartment.Disconnect the air-supply line. are not leaking.Watch for active air bubbles,which indicate a leak. <br /> 3.5.2.4.Monitor the pressure for one hour.Do not release air 3.6.2.5.Monitor the pressure for one hour.Do not release air <br /> pressure. <br /> pressure. <br /> 7 <br />