Laserfiche WebLink
Tank Assessmeni per 22 CCR 66295.192(k) <br /> 1) Tank Confi ration: <br /> Above ground"lube cube" steel tank with integral secondary containment, with <br /> approximately 500 gallon capacity. <br /> 2) Design Stand rds: <br /> a) Steel Ta <br /> b) Material t ickness not available. Tank is in good condition with original pain <br /> finish stil intact. suction end. <br /> d) External s ction pump mounted to top of tank with secondary containment pan. <br /> Air opera ed diaphragm pump. <br /> e) Tank drai 'ng see exhibit "A". <br /> 3) Documented a e of tank system, not available. Estimated age to be 10 years old. <br /> 4) Leak Detectio E ui ment: <br /> Tank is equipp d with automatic shut-off and over fill alarm, and a monitor in <br /> secondary cont inment space. <br /> 5) Corrosion Pro ection: <br /> Steel tank hasriginal epoxy coating. <br /> 6) Spill Preventi or Overfill Equipment: <br /> The tank has in egral secondary containment, which is monitored. The suction line is <br /> continuous wit welded joints. An overfill alarm and automatic shut-off provided <br /> just inside the all adjacent to tank location. <br /> 7) Secondary Co tainment for the Tank System: <br /> The tank has integral secondary containment(double wall tank), and the welded <br /> copper suction 1'ne is considered "joint-less". The pump is mounted within <br /> secondary contanment pan. <br /> 8) Hazardous Ch racteristics of the Waste: <br /> Waste oil is cobustible, and is toxic. <br /> 9) Results of a Vi ual Inspection: <br /> The tank, pipin and ancillary equipment has been visually inspected. There is no <br /> evidence of wel cracks, scrapes of protective coatings, corrosion or structural <br /> damage. <br /> 10) Results of Ti h ess Test: <br /> An inspection h s been performed to verify the integrity of the waste oil system. The <br /> pressurized syst m and vented tank have no leaks. <br />