Laserfiche WebLink
Tank Width: 3'-9" (interior) <br /> Tank Height: 4'-11" (interior) <br /> Tank Gross Capacity: 500 gallons <br /> Spill Prevention or Overfill Equipment , . <br /> Tank is equipped with a high level sensor which will actuate a normally <br /> open solenoid valve to interrupt the air supply to the pneumatic transfer <br /> pump if the level is above set point. <br /> Secondary Containment Assessment Page B: <br /> Overhead and Cross Sectional View: <br /> Please see Appendix "A" and "B" <br /> Secondary Tank Volume Calculations <br /> Tank Length: 4'-0" (interior) <br /> Tank Width: 4'-0" (interior) <br /> Tank Height: 4'-11" (interior) <br /> Tank Gross Capacity: 575 gallons <br /> The secondary containment calculations provided for on this page are for <br /> secondary containment systems that utilize a double walled tank for <br /> containment. <br /> Overhead and Cross-Sectional Views: <br /> Please see Appendix "A" and "B" <br /> Design of tank: 611 <br /> This is a double wall construction fabricated ASTM A-36 steel tank <br /> with an epoxy coating protecting the exterior from corrosion and no <br /> inner coating. Leak detection is provided by a daily documented <br /> inspection by the service facility staff. <br /> Visual inspection of containment area- <br /> The capacity is 575 gallons. It is capable of providing more than <br /> 100% secondary containment of the primary tank and ancillary <br /> equipment volume of 504 gallons per 192(1)(1). The material is <br /> 6 <br />