Laserfiche WebLink
' 11D 2nd Avenue South 1t D7,Pacheco CA�941 �1611 �McCampbell A1lalytical Inc Telephone 925 748162DFax 925I http//w4v��mccampbell in - (� <br /> QC SUMMARY REPORT FOR SW8015C <br /> Matrix W WorkOrder 0212472 <br />' EPA Method SW8015C Extraction SW3510C BatchlD 5503 Spiked Sample ID N/A <br /> Sample Spiked MS* MSD* MS-MSD* LCS LCSD LCS-LCSD Acceptance Catena(%) <br /> Compound --- ---— - <br />' pg/L pg/L °/a Rec %Rec %RPD %Rec 6/°Rec %RPD Low High <br /> TPl I(d} N/A 7500 N/A N/A N/A 113 113 00996 70 130 <br /> ' %SS N/A 100 N/A N/A NIA 115 114 0 296 70 130 <br /> All target compounds in the Method Blank of this extraction batch were ND less than the method RL with the following exceptions <br /> NONE <br /> 1 <br /> 1 <br /> MS=Matrix Spike MSD=Matrix Spike Duplicate LCS=Laboratory Control Sample,LCSD=Laboratory Control Sample Duplicate RPD=Relative Percent <br /> ' Deviation <br /> N/A�not enough sample to perform matrix spike and matnx spike duplicate <br /> NR=analyte concentration in sample exceeds spike amount for sod matrix or exceeds 2x spike amount for water matrix or sample diluted due to high matrix or <br /> analyte Content <br /> ' %Recovery=100*(MS-Sample)!(Amount Spiked) RPD=100*(NIS--MSD)1(MS+MSD)*2 <br /> *MS and/or MSD spike recoveries may not be near 100%or the RPDs near 0%if a)the sample is inhomogenous AND contains significant concentrations of <br /> ' analyte relative to the amountspiked,or b)if that specific sample matrix interferes with spike recovery <br />