Laserfiche WebLink
08/22/1997 15:57 5102772361 TOSCO ENVIRONMENTAL PAGE 09 <br /> Triangle Environmental, Inc. <br /> T.E.I.SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Unocal #31010 <br /> Tank #: i Test Date: 7/21/97 <br /> Product: Unleaded Regular Work N: 460094 <br /> Test Method: System 5000 Test Method: R.J.FTA <br /> Capacity: 15000 Manufacturer: Vaporleae <br /> Diamew(in): 107 <br /> LID Model: LD4000 <br /> Product Level(in): 69 LID Serial#: 47630 <br /> Liquid Volume(Gals): 9886 Line Drain Hack(ml): 150 <br /> Liquid Percent(°/a): 65.90A L/D Trip Time(sec): 3 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 14 <br /> Coef.of Expansion: 0.000650 Metering Pressure(psi): 29 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): 0 <br /> LID Result: PASS <br /> Product Temp. (F): 83 <br /> Head Pressure(psi): 1.9 <br /> Test Start Time: 10:30:00 PM <br /> Test End Time: 10.45:00 PM Test Method: TEI LT-3 <br /> Test Rate(gph): 0.02 Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 9:00:00 PM <br /> Test Method: ULLAGE Line End Time: 9:15:00 PM <br /> UllageVolurne(gale.): 5114 Line Start Level: 60 <br /> Ullage Test Time: 10:30:00 PM Line End Level: 60 <br /> Ullage Vacuum(psi): 2.9 Line Test Rate(gph): 0.000 <br /> Ullage Result: PASS Line Test Result: PASS <br /> , <br /> 2 <br />