Laserfiche WebLink
08/22/1997 15:57 5102772361 TOSCO ENVIRONMENTAL PAGE 10 <br /> Triangle Environmental, Inc. <br /> T.E.I.SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Unocal #31010 <br /> Tank##: 2 Test Date: 7/21/97 <br /> Product: Unleaded Premium Work*: 4600S4 <br /> Test Method: System 5000 Test Method: R.I.FTA <br /> Capacity: 15000 Manufacturer: Vaporless <br /> Diameter(in): 107 L/D Model: LD-2000 <br /> Product Level(in): S6 L/D Serial N: 47632 <br /> Liquid volume(Gals): 7643 Line Drain Back(ml): 160 <br /> Liquid Percent('/o): 51.09/, LID Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 15 <br /> Cod.of Expansion: 0.000650 Metering Pressure(psi): 28 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.9 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 80 <br /> Head Pressure(psi): 1.5 <br /> Test Start Time: 10:50:00 PM <br /> Test End Time: t 1:00:00 PM Test Method: TEI LT-3 <br /> Ten Rate(gph): 0.02 Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 9,00:00 PM <br /> Test Method: ULLAGE Line End Time: 9:15:00 PM <br /> UllageVolume(gals.): 7357 Line Start Level: 130 <br /> Ullage Test Time: 10:50:00 PM Line End Level: 130 <br /> Ullage Vacuum(psi): 2.5 Line Test Rate(gph): 0.000 <br /> Ullage Result: PASS Line Test Result: PASS <br /> r <br /> 3 <br />