Laserfiche WebLink
VO/LL/1"I 1b:b/ 5102772361 TOSCO ENVIRONMENTAL PAGE 11 <br /> 1 <br /> Triangle Environmental, Inc. <br /> T.E.I.SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Unocal #31010 <br /> Tank#: 3 Test Date: 7/21/97 <br /> Product: Diesel Worke: 460084 <br /> Test Method: System 5000 Test Method: R.J.ETA <br /> Capacity: 12000 Manufacturer. Vaporless <br /> Diameter(in): 93 L/D Model: LD-2000 <br /> Product Level(in): 34 L/D Serial M: 47631 <br /> Liquid Volume(Gals): 3848 Line Drain Hack(ml): I60 <br /> Liquid Percent(°/v): 32.1% L/D Trip Time(aec): 2 <br /> Specific Gravity: 0.850 Holding Pressure(psi): 16 <br /> Coef.of Expansion: 0.000650 Metering Pressure(psi): 29 <br /> Water On Tank(in): 0 L!D Test Rate(gph): 2.2 <br /> Water in Tank(in): 0 LID Result: PASS <br /> Product Temp. (F): 79 <br /> Head Pressure(Psi): 1.0 <br /> Test Start Time: 11:10:00 PM <br /> Test End Time: 1120:00 PM Tea Method: TET LT-3 <br /> Test Rate(sph): 0.02 Pump Brand: Red lacket <br /> Test Result: PASS System Type: Presstnt <br /> Line Presaurc(psi): 50 <br /> Line Start Time: 9:30:00 PM <br /> Test Method: ULLAGH Line EndTime, 9:43:09 PM <br /> Ultagevelum.(Sols): 8152 Line Start Level: 300 <br /> Ullage Test Time: 11:10:00 PM Line End Level: 300 <br /> tillage Vacuum(psi): 2 Line test Rate(gph): 0.000 <br /> Ullage Remit: PASS Line Test Result: PASS <br /> t <br /> 4 <br />