Laserfiche WebLink
F— Ripon USD <br /> :0 <br /> 304 N. Acacia Ave. <br /> Ripon, CA <br /> UL 2085 Primary Tank <br /> 10,000 Gallon Time Pressure AP <br /> ConVault 0 10 psi 0 <br /> 5 3.0 EL.- 0 <br /> UL # M651168 10 3.0 si 0 <br /> 15 3.0 psi 0 <br /> 20 3.0psi 0 <br /> 26 3,0 psi 0 <br /> 30 3.0 psi 0 <br /> 35 3.0 psi 0 <br /> 40 .3.0 psi 0 <br /> 45 3.0 psi 0 <br /> 50 10 psi 0 <br /> 55 3-0 psi 0 <br /> 60 3,0 psi 0 <br /> Industry Standards certification testing was performed on March 6, 2019, at Ripon <br /> USD located at 304 K Acacia Ave., Ripon, CA 95366. "resting was performed to <br /> Industry Standards on the 10,000 Gallon #2 Diesel Fuel tank and the internal <br /> (primary) tank was tested to 3,0 psi as the tank was half full. The primary tank <br /> passed it's Industry Standards ccrtification testing. No defects were observed and <br /> the 10,000 Gallon #2 Diesel Fuel system was observed to be in compliance with <br /> Industrial Standards testing requirements- <br /> Test Device: -Ashcroft T5500 SS 0-5 psi Pressure Gauge­_ <br /> Test Gas: ­Nitrogen Gas- ................ <br /> Test Pressure: ­3.0 psi_ <br /> Test Duration: 60 minutes," <br /> Tank Capacity. .....10,000 Gallons <br /> Tank Volumne 5,000 Gallons <br /> Certified Tester, Gary Reevovs­.. <br /> REA #30349 <br /> 1CC #8019664 <br /> SPOO1 Level I1 #11111 <br /> NDT-UT Level 1114-001 <br /> . .................. <br />