Specifications (Continued) <br />2.2.4 Regulated Release Mechanism: The regulated <br />release mechanism shall be a spring-loaded, <br />mechanical/pneumatic type capable of provid- <br />ing the expellant gas supply to one or two agent <br />tanks depending on the capacity of the gas <br />cartridge used or three 3.0 gallon (11.4 L) agent <br />storage tanks in certain applications. It shall <br />contain a factory installed regulator deadset at <br />110 psi (7.6 bar) with an external relief of approx- <br />imately 180 psi (12.4 bar). <br />It shall have the following actuation capabili- <br />ties: automatic actuation by a fusible link detec- <br />tion system and remote manual actuation by a <br />mechanical pull station. <br />The regulated release mechanism shall contain <br />a release assembly, regulator, expellant gas <br />hose, and agent storage tank housed in a stain- <br />less steel enclosure with cover. The enclosure <br />shall contain knock-outs for 1/2 in. conduit. The <br />cover shall contain an opening for a visual status <br />indicator. <br />It shall be compatible with mechanical gas shut- <br />off devices; or, when equipped with a field or <br />factory-installed switch(es), it shall be compat- <br />ible with electric gas line or appliance shut-off <br />devices, or connections to a building fire alarm <br />control panel. <br />2.2.5 Regulated Actuator Assembly: When more than <br />two agent tanks or three agent tanks in certain <br />applications are required, the regulated actua- <br />tor shall be available to provide expellant gas <br />for additional tanks. It shall be connected to the <br />cartridge receiver outlet of the regulated release <br />mechanism providing simultaneous agent <br />discharge. The regulator shall be deadset at <br />110 psi (7.6 bar) with an external relief of <br />approximately 180 psi <br />(12.4 bar).The regulated actuator assembly <br />shall contain an actuator, regulator, expellant <br />gas hose, and agent tank housed in a stainless <br />steel enclosure with cover. The enclosure shall <br />contain knockouts to permit installation of the <br />expellant gas line. <br />2.2.6 Discharge Nozzles: Each discharge nozzle shall <br />be tested and listed with the 6-102 system for <br />a specific application. Nozzles tips shall be <br />stamped with the flow number designation <br />(1/2, 1, 2, or 3). Each nozzle shall have a metal <br />or rubber blow-off cap to keep the nozzle tip <br />orifice free of cooking grease build-up. <br />2.2.7 Distribution Piping: Distribution piping shall be <br />Schedule 40 black iron, chrome-plated, or stain- <br />less steel conforming to ASTM A120, A53, or <br />A106. <br />2.2.8 Detectors: The detectors shall be the fusible <br />link style designed to separate at a specific <br />temperature, or shall be electric thermal detec- <br />tors designed to operate at a factory preset <br />temperature. <br />2.2.9 Cartridges: The cartridge shall be a sealed <br />steel pressure vessel containing either carbon <br />dioxide or nitrogen gas. The cartridge seal shall <br />be designed to be punctured by the releasing <br />device supplying the required pressure to expel <br />wet chemical agent from the storage tank. <br />2.2.10 Agent Distribution Hose: An optional agent <br />distribution hose shall be available for kitchen <br />appliances manufactured with or resting an <br />casters (wheels/rollers). This shall allow the <br />appliance to be moved for cleaning purposes <br />without disconnecting the appliance fire <br />suppression protection. Hose assembly shall <br />include a restraining cabie kit to limit the appli- <br />ance movement within the range (length) of the <br />flexible hose. <br />2.2.11 Flexible Conduit: The manufacturer supplying <br />the Restaurant Fire Suppression System shall <br />offer flexible conduit as an option to rigid EMT <br />conduit for the installation of pull stations and/ <br />or mechanical gas valves. The flexible conduit <br />shall be UL Listed and include all approved <br />components for proper installation. <br />2.2.12 Pull Station Assembly: The Fire Suppression <br />System shall include a remote pull station <br />for manual system actuation. The pull station <br />shall be designed to include a built-in guard to <br />protect the pull handle. The pull station shall <br />also be designed with a pull handle to allow for <br />three finger operation and shall be red in color <br />for quick visibility. <br />3.0 IMPLEMENTATION <br />3.1 Installation <br />3.1.1 The R-102 fire suppression system shall be <br />designed, installed, inspected, maintained, and <br />recharged in accordance with the manufactur- <br />er's listed instruction manual. <br />3.2 Training <br />3.2.1 Training shall be conducted by representatives <br />of the manufacturer. <br />Note: The converted values in this document are for dimensional reference <br />only and do not reflect an actual measurement. <br />ANSUL, R-102, and the product names listed in this material are marks and/ <br />or registered marks. Unauthorized use is strictly prohibited_